Bosch Uni Condens 8000 F UC8000F Operating Instructions Manual Download Page 6

Product Information

 

Uni Condens 8000 F – 6720867069 (2016/10)

6

Oil burner

Oil burners used must be suitable for low sulphur fuel oil. Observe the 
manufacturer's oil burner selection list and the burner manufacturer's 
instructions.

Permissible fuels:
• Low-sulphur extra-light fuel oil with a sulphur content < 50 ppm and 

a proportion of bio-oil (FAME) ≤ 10 %.

Existing residual amounts of fuel oil with a sulphur content ≥ 50 ppm 
must be pumped out and the oil tank cleaned.

Type tested dual burners can also be used. The requirements for the gas 
side and the oil side described above also apply here. All products 
subsequently described apply equally for the gas side and oil side.

2.7

Operation conditions

Observe the maximum rated heat input Qn (Hi) specified on the data 
plate when setting the burner output.

Table 2   Operation conditions

Table 3   Operation conditions

It must be possible to check the number of burner starts, e.g. at the user 
interface, third-party control unit, building control system or burner 
control unit.

2.8

Requirements for the control unit

We recommend using a control unit from the CFB 800/CFB 900 or 
CC 8000 series.

The purpose of optimum control unit settings is to achieve long burner 
runtimes and avoid rapid temperature changes in the boiler. Gentle 
temperature changes result in a longer service life of the heating system. 
The control strategy of the control unit must therefore be prevented from 
becoming ineffective, i.e. through the boiler temperature controller 
switching the burner on and off.

Observe the following points when selecting the control unit.
• The control unit must ensure that the maximum internal boiler water 

temperature and the high limit safety cut-out are at least 5 K apart.

• It must also be ensured that the control electronics rather than the 

boiler temperature controller switch the burner on and off.

• The control unit must ensure that the burner is switched to low load 

before a controlled shutdown. If this is not observed, the safety shut-
off valve (SAV) in the gas train may lock out.

• Select and adjust the control unit so as to allow a gentle start-up of 

the boiler with a time delay when the system is cold. The heat energy 
demand must only be switched on with time delay.

• After the burner demand, an automatic timer (for example) should 

limit the burner to low load for a period of approx. 150 seconds. A 
restricted heat demand will prevent uncontrolled starting and 
stopping of the burner.

• It must be possible to show the number of burner starts at the control 

unit used (or alternatively at the burner control unit).

• The maximum number of burner starts must be monitored. There 

should be a maximum of 6 burner starts per hour (averaged over 
burner runtime on one day). If the number of starts is higher, the user 
should be notified. The system must be checked to find out whether 
the number of burner starts can be reduced. The customer service of 
the manufacturer can provide assistance with optimisation of the 
system.

2.9

Burner requirements

Only use specified pressure-jet gas burners with floor standing gas 
condensing boilers.
Use specified pressure-jet burners or dual fuel burners for floor standing 
gas/oil condensing boilers.

The boiler must be equipped with a burner that is suitable for the boiler.

NOTICE: 

System damage through the use of an incorrect burner.

▶ Only use burners which meet the technical boiler requirements.

Any pressure-jet gas burner type-tested to EN 676 can be used if its 
operating range matches the boiler specifications. Oil burners type-
tested to EN 267 can be used if they have been approved by the 
manufacturer for low sulphur fuel oil (s < 50 ppm) and if their operating 
ranges match the specification of the boiler. Only burners that have been 
tested and approved for electromagnetic compatibility (EMC) may be 
used.

Operation conditions

Unit

Value

Maximal permissible temperature of 
high limit safety cut-out /(STB)

°C

110

Maximum operating pressure

bar

Dependent on boiler 
size

Maximum number of burner starts

per 
annum

15 000

Operation conditions Uni Condens 8000 F 

800...1200 with 
modulating 
operation

Uni Condens 8000 F 
800...1200 with 
constant boiler 
temperature

Volumetric flow rate

None –
In conjunction with a 
CFB/CC control unit 
for modulating 
operation (CFB 840; 
CFB 810; CFB 830 or 
CC 8311; CC 8312). 

None 
In conjunction with a 
CFB/CC control unit 
for constant boiler 
temperature CFB 810 
or CC 8312, or when 
supplemented by a 
third party control 
unit.

Min. boiler water 
temperature

Operating Interruption 
(complete boiler shut-
down)

Heating circuit control 
unit with heating mixer

Minimum return 
temperature

Miscellaneous

1)2)

1) Maximum 15,000 burner starts per year. In order not to exceed the number of 

burner starts, observe the information on setting the control unit and burner in 
the technical guide or installation instructions. If this value is still however 
exceeded, please contact the customer service of the manufacturer.

2) The number of burner starts per year is influenced by the boiler system's 

operating settings (control parameters in the boiler control and the combustion 
setting) and by the design of the boiler system with regard to the consumer's 
heat requirement. To avoid exceeding the number of burner starts per year as a 
result of operating settings that have not been optimised, the manufacturer 
offers complete commissioning and regular system inspections for boilers, 
burners and boiler controls (CFB/CC controllers with function modules).

1)

Summary of Contents for Uni Condens 8000 F UC8000F

Page 1: ...6720867069 2016 10 GB IE Operating instructions for users Floor standing condensing boiler Uni Condens 8000 F UC8000F 800 1200 kW ...

Page 2: ...heating controller etc prior to operation Observe the safety instructions and warnings 1 Explanation of symbols and safety instructions 2 1 1 Explanation of symbols 2 1 2 General safety instructions 2 2 Product Information 4 2 1 Declaration of Conformity 4 2 2 Determined use 4 2 3 Symbol at the boiler 4 2 4 Data plate 4 2 5 Product Description 4 2 6 Permissible fuels 5 2 7 Operation conditions 6 2...

Page 3: ...lified person so that risks are avoided H Risk through oil leaks If using oil as fuel country specific regulations hold the operator responsible for asking a contractor to correct any oil leaks the moment they are discovered H If you smell gas Close gas isolation valve Open windows and doors Do not touch any electrical switch telephone and do not use outlets Extinguish any naked flames Do not smok...

Page 4: ...ity for this product For this see the contact address on the back cover of these instructions 2 2 Determined use The Uni Condens 8000 F 800 1200 floor standing condensing boiler has been designed for wet heating systems in e g apartment buildings or industrial applications The boiler is only approved for open flue mode When installing and operating the heating system Comply with standards regulati...

Page 5: ...ure return 14 Inspection opening on the water side both sides 15 Flow safety line 16 Heating flow 17 Boiler safety assembly accessories 18 Lifting points 2 6 Permissible fuels The boiler must only be operated with the specified fuels Only burners that are suitable for the specified fuels may be used Gas burner The combustion of biogas is not permitted Permissible fuels Natural gas from the public ...

Page 6: ...ere should be a maximum of 6 burner starts per hour averaged over burnerruntimeononeday Ifthenumberofstartsishigher theuser should be notified The system must be checked to find out whether thenumberofburnerstartscanbereduced Thecustomerserviceof the manufacturer can provide assistance with optimisation of the system 2 9 Burner requirements Only use specified pressure jet gas burners with floor st...

Page 7: ...d guidelines Observe the information on the data plate of the boiler 3 1 Combustion air quality To avoid corrosion keep the supply of combustion air free of corrosive substances e g halogenated hydrocarbons that contain chlorine or fluorine compounds Never use or store chlorinated cleaning agents or halogenated hydrocarbons as contained in spray cans solvents or cleaning agents paints and adhesive...

Page 8: ... e g due to a fault shutdown and there is a risk of frost drain the heating water at the DFV Also leave the air vent at the highest point in the heating system open 5 1 Shutting down the heating system The heating system is shut down via the control unit The burner is also automatically shut down Switch off the burner at the control unit 5 2 Shutting down the heating system in an emergency Only sw...

Page 9: ...nted correctly Check the heating system for leaks and the expansion vessel for functionality Observe the requirements regarding water quality operator s log If water loss occurs frequently locate the cause and rectify the problem without delay NOTICE System damage due to temperature stresses Onlyfilltheheatingsystemwhencold theflowtemperaturemustnot exceed 40 C During operation only fill the heati...

Page 10: ...Further information on the fault displays can be found in the service instructions of the relevant controlunit Inaddition burnerfaultsaresignalledbyanindicatoronthe burner Press burner reset button see operating instructions of burner and control If the burner still fails to start after three attempts contact a contractor 8 2 Other faults For other possible faults see the installation and operatin...

Page 11: ......

Page 12: ...Bosch Thermotechnik GmbH Junkersstrasse 20 24 D 73249 Wernau www bosch thermotechnology com ...

Reviews: