Product Information
5
Uni Condens 8000 F – 6720867069 (2016/10)
Fig. 1
Boiler overview
[1]
Boiler shell
[2]
Burner door
[3]
Locking lug to secure the load during transportation
(not a lifting eye)
[4]
Flue gas collector
[5]
Condensate, siphon
[6]
Drain
[7]
Base frame rail
[8]
Control unit (accessory)
[9]
Cable conduit
[10] Flue gas connection
[11] Inspection aperture of condensation heating surface
[12] Port Return 1 (RK1) low temperature return (main return)
[13] Return connection 2 (RK2), high temperature return
[14] Inspection opening on the water side (both sides)
[15] Flow safety line
[16] Heating flow
[17] Boiler safety assembly (accessories)
[18] Lifting points
2.6
Permissible fuels
The boiler must only be operated with the specified fuels. Only burners
that are suitable for the specified fuels may be used.
Gas burner
The combustion of biogas is not permitted.
Permissible fuels:
• Natural gas from the public gas supply in accordance with national
regulations with a total sulphur content < 50 mg/m
3
• LPG in accordance with national regulations with a content of
elementary sulphur < 1.5 ppm and volatile sulphur < 50 ppm