Troubleshooting
|
25
TW Series Water to Water
6720220047 (2016/02)
Revised 02-16
ELECTRICAL DATA TABLE
Models
Voltage
Code
Rated
Voltage
Voltage
Min/
Max
Compressor
QTY
RLA
LRA
Min
Circuit
Amps
Max
Fuse/
HACR
TW025
1
208-230/60/1
197/253
1
11.7
58.3
14.6
25
TW035
1
208-230/60/1
197/253
1
15.3
83.0
19.1
30
TW049
1
208-230/60/1
197/253
1
21.2
104.0
26.5
45
TW061
1
208-230/60/1
197/253
1
27.1
152.9
33.9
60
TW071
1
208-230/60/2
197/254
1
29.7
179.2
37.1
60
TW122
1
208-230/60/1
197/253
2
28.3
178.0
63.7
90
UPM Board LED Indications
Indication
Color
Blinks
Description
GREEN
Solid
18-30 VAC Power is present
RED
1
High pressure lockout
RED
2
Low pressure lockout
RED
3
Freeze sensor lockout
RED
4
Condensate overflow
RED
5
Brownout
RED
6
Evaporator Freeze condition