SSB
6720866940 (2017/11) US
Control Panel (LCD Display) | 15
Press “OK” and the display
will show the
following information:
• Supply Temperature
•
Return Temperature
•
DHW Temperature [Sensor must be connected to show a value. If not,
the default value will appear]
•
Outside Temperature
•
Flue Temperature [Sensor must be connected to show a value. If not,
the default value of 14°F
will appear]
•
System Temperature [Sensor must be connected to show a value. If
not, the default value will appear]
• Fan Speed
•
Ionization
• State
• Error
The display shows four lines at a time:
Boiler Status
Flow Temperature
115.0 °F
Return Temperature
110.0 °F
DHW Temperature
111.0 °F
Outside Temperature
50.0 °F
Fig. 37
To scroll the screen use the “UP/DOWN” keys “
/
”.
5 .5
Outdoor reset (Climatic compensation)
To set the outdoor reset curve enter “Central Heating (CH)” menu and
press “OK”.
The display will appear as follow:
Outdoor reset
Setp. [°F]
194
32
5
95
Des. Supply T.
180°F
Bas. Supply T.
104°F
WW Shutdown
70°F
Bas. Outd. T.
70°F
T_Outside [°F]
Des. Outd. T.
25°F
Fig. 38
“Des. Supply T” and “Des. Outd T” will be highlighted, to change either
value press “OK”:
•
Use UP/DOWN arrows to change the “Des. Supply T”. Use the LEFT/
RIGHT arrows to change the “Des Outd. T”
•
Press “OK” to save changes
•
Use the LEFT/RIGHT arrows to select the other values
Repeat steps to make additional changes
Once set the parameters press “ESC” to exit the menu.
5 .6
Parameters list
To have access to the parameter list press “menu” button and select
“Settings” using the “UP/DOWN” keys “
/
”.
Menu
Domestic Hot Water
Information
Settings
System Test
Fig. 39
Press the “OK” button and select “Boiler Settings” using the “UP/DOWN”
keys “
/
”.
Settings
General Settings
Boiler Settings
Fig. 40
Press the “OK” button. At this point a password is requested [Password
is required for boiler settings only]:
Password
0
* * *
Fig. 41
Enter one digit at a time using the UP/DOWN” keys “
/
” to increase/
decrease the value. When the value is correct then press “OK”.
In the system there is a password for the
two
levels:
•
Level 1 USER: no password needed (0000)
•
Level 2 INSTALLER: password “0300”