2.21 Bell
Test
Press and hold the [2] key until two beeps sound.
The piezo siren sounds for 2 seconds.
2.22 Strobe Test (Toggle On/Off)
1. To turn the strobe on, press and hold the [3]
key until three beeps sound.
2. To turn the strobe off, press and hold the [3]
key until two beeps sound.
2.23 Telco Arm Sequence (Call
Forward On)
1. Enter the Installer Code or Master Code
followed by the [3] and [#] keys (for example,
[1 2 3 4 3 #]).
2. Enter [1 #].
3. Enter the Call Forward On sequence.
4. Press the [#] key to exit.
2.24 Telco Disarm Sequence (Call
Forward Off)
1. Enter the Installer Code or Master Code
followed by the [3] and [#] keys (for example,
[1 2 3 4 3 #]).
2. Enter [2 #].
3. Enter the Call Forward Off sequence.
4. Press the [#] key to exit.
3.
Programming
Parameters
Shaded options indicate default
values.
3.1 Telephone
Programming
3.1.1
Phone Number 1 - Receiver 1
Location
000 to 015
Default
0
0 = 10 and telephone termination = 0
Anywhere else 0 = 0
3.1.2
Phone Number 2 - Receiver 1
Location
016 to 031
Default
0
0 = 10 and telephone termination = 0
Anywhere else 0 = 0
3.1.3
Handshake Tone for Receiver 1
Location
032
1
HI-LO handshake (contact ID)
2
1400 Hz (Ademco TX @ 1900 Hz)
3
2300 Hz (Sescoa TX @ 1800 Hz)
4 No
handshake
5 Pager
3.1.4
Transmission Format for Receiver 1
Location
033
1
Contact ID
2
4 + 2 expressed
3
FSK 300 baud
4 Domestic
5 Basic
pager
3.1.5
Subscriber ID Number for Receiver 1
Location
034 to 039
Default
0
Right justified
3.1.6
Phone Number 1 - Receiver 2
Location
040 to 055
Default
0
0 = 10 and telephone termination = 0
Anywhere else 0 = 0
3.1.7
Phone Number 2 - Receiver 2
Location
056 to 071
Default
0
0 = 10 and telephone termination = 0
Anywhere else 0 = 0
3.1.8
Handshake Tone for Receiver 2
Location
072
1
HI-LO handshake (contact ID)
2
1400 Hz (Ademco TX @ 1900 Hz)
3
2300 Hz (Sescoa TX @ 1800 Hz)
4 No
handshake
5 Pager
3.1.9
Transmission Format for Receiver 2
Location
073
1
Contact ID
2
4 + 2 expressed
3
FSK 300 baud
4 Domestic
5 Basic
pager
3.1.10
Subscriber ID Number for Receiver 2
Location
074 to 079
Default
0
Right justified
3.1.11 Dialling
Format
Location
080
1
Australian DTMF
2 Australian
decadic
3
Alternate DTMF and Australian decadic
4 International
DTMF
5 Reversed
decadic
6
Alternate DTMF and reversed decadic
3.1.12 Reserved