Bosch Rexroth AG
VT-MSFA1 | RE 30260-B/07.12
General warnings of damage to property and damage to the product
wARnInG
High electrical voltage by incorrect connection!
Danger to life, risk of injury caused by electric shock.
f
De-energize the relevant system part for all works and secure it against restarting.
f
All connections and terminals with voltages between 0 and 50 Volt may only
be connected with devices, electric components and lines with a protective
extra-low voltage (PELV).
f
Only connect voltages and electric circuits provided with a safe isolation from
dangerous voltages. Safe isolation can be achieved, for example, by isolating
transformers, safe optocouplers or mains-free battery operation.
Stroke of lightning!
Risk of uncontrolled machine movements.
f
An incorrect earthing concept or potential equalization may lead to damage
to the electronics. Provide for potential equalization for the device.
Failures and errors in the control circuits or the energy supply!
Risk of uncontrolled machine movements.
f
Comply with the safety according to EN ISO 13849 or IEC 62061.
CAUTIOn
Hot surfaces!
Risk of burning.
f
System parts may become hot during operation. Allow the system parts to
cool down before touching them or wear protective gloves.
3 General warnings of damage to property
and damage to the product
NOTICE
High voltage!
Possible damage to the booster amplifier.
f
Only wire the booster amplifier in the de-energized condition.
High temperatures!
Possible damage to the booster amplifier.
f
Do not use free-wheeling diodes in the solenoid conductors!
wrong cables! Voltage loss, melting of the cable!
Risk of product damage.
f
For solenoid conductors up to a length of 10 m, the wire cross-section must
be 1.5 mm
2
, for lengths from 10 - 25 m 2.5
mm
2
. With greater lengths, please
contact us!