XD01, mains connection
Important notes
Lethal electric shock by live parts with more
than 50 V!
WARNING
Only operate the device
●
with the connectors plugged on (even if no lines have been connected
to the connectors) and
●
with the equipment grounding conductor connected!
Risk of damage to the device!
NOTICE
Provide strain relief for the terminal connectors of the device in the control
cabinet.
XD01, mains connection (35 mm
2
)
View
Identificati
on
Function
L1
Connection to power grid (L1)
L2
Connection to power grid (L2)
L3
Connection to power grid (L3)
Terminal block
Unit
min.
max.
Connection cable
Stranded wire
mm
2
0.5
35
AWG
20
4
Stripped length
mm
18
Tightening torque
Nm
2.5
4.5
Occurring current load and minimum required
connection cross section
See technical data of device used (I
LN
and A
LN
)
Occurring voltage load
See technical data of device used (U
LN
or U
LN_nenn
)
Tab. 10-4:
Function, pin assignment, properties
IndraDrive X Drive Controllers Power Sections XCS1, XMD1,
XMQ1
71/123
Mounting, dismounting and electrical installation
R911392532_Edition 01 Bosch Rexroth AG