Never run lines of one of these areas in parallel with lines of another area so
that there is no unwanted interference injection from one area to the other
and that the filter is jumpered with regard to high frequency. Use the shortest
possible connecting lines.
Recommendation for complex systems: Install drive components in one
cabinet and the control units in a second, separate cabinet.
Badly grounded control cabinet doors act as antennas. For this reason,
connect the control cabinet doors to the cabinet on top, in the middle and on
the bottom with short equipment grounding conductors with a cross section of
at least 6 mm
2
or, even better, with grounding straps of the same cross
section. Make sure connection points have good contact.
Control cabinet design according to interference areas - exemplary ar‐
rangements
Do not operate any additional loads at the mains filter!
Do not run any other loads at the connection from the mains filter
output to the mains connection of the supply unit.
For motor fans and power supply units, for example, use separate
mains filters.