9-4
Control Mains Contactor
Rexroth IndraDrive
DOK-INDRV*-HMV-*******-PR01-EN-P
Without DC Bus Dynamic Brake
•
If an uncontrolled running out of the drives cannot damage the
installation.
•
If only asynchronous drives are connected to the supply unit.
•
If the end positions of the feed axes are sufficiently attenuated.
The DC bus voltage is not short-circuited.
In an emergency stop situation, or if the monitors of the supply unit are
actuated (e.g., power failure), then the drives are shutdown by the drive
electronics as per the set error reaction.
The mains contactor in the supply unit immediately falls off when the
emergency stop sequence is initiated. The drive enable is removed by the
emergency stop relay or by an auxiliary contact of the mains contactor.
The drives are shutdown depending on the set error reaction.
CAUTION
Machine damages due to brakeless slowing
down of the drives in the event of faulty drive
electronics!
⇒
Use motors with mechanical brakes (a holding brake
must not be used as operating brake).
⇒
End positions of feed axes must be sufficiently
attenuated.
Application
Features
Function
Summary of Contents for Rexroth IndraDrive HMV01.1E-W0030
Page 30: ...5 2 Transport and Storage Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 40: ...6 10 Mechanical Mounting Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 88: ...9 8 Control Mains Contactor Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 122: ...13 22 Appendix Rexroth IndraDrive DOK INDRV HMV PR01 EN P Fig 13 25 HFD01 2 480 0026 ...
Page 123: ...Rexroth IndraDrive Appendix 13 23 DOK INDRV HMV PR01 EN P Fig 13 26 HFD02 2 480 0026 ...
Page 130: ...14 6 Index Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 131: ......