Loss of CE conformity due to modifications at the device.
CE marking applies only to the device upon delivery. After modifying
the device, verify the CE conformity.
7.2 UL/CSA certified
The devices are certified acc. to
●
UL508 (Industrial Control Equipment) and
●
C22.2 no. 142-M1987 (CSA)
UL file no. E210730
However, there can be combinations or extension stages with a limited or miss-
ing certification. Thus, verify the registration according to the UL marking on the
device.
Loss of UL/CSA conformity due to modifications at the device.
UL and CSA marking applies only to the device upon delivery. After
modifying the device, verify the UL and the CSA conformity.
8 Technical data
Degree of protection
IP 20
Weight
0.54 kg
Tab. 8-1: Degree of protection and weight
8.1 Voltage supply
Nominal input voltage
24 V DC (use a 24 V power supply unit acc. to DIN
EN 60742, classification VDE 0551, for example
the power supply unit VAP01.1H-W23-024-010-
NN, part number R911171065)
Input voltage range
24 V DC +20 %, -15 %
Emitted interference and surge immunity
U
max
= 35 V (for t < 100 ms)
Current consumption at U
N
Max. 0.45 A at 24 V
Input fuse
None
Switch-on threshold
22 V ±5 %
Switch-off threshold
19 V ±5 %
10/33
Technical data
IndraControl VAC 08.1 CDI+ Splitter
Bosch Rexroth AG R911400465_Edition 01
Summary of Contents for rexroth IndraControl VAC 08.1