Settings Customer level

Rego 1000 – 6 721 831 662 (2021/03) en

13

6.4

Holiday

During holidays (absence), the heating can, for example, be kept at a 
lower or higher level and hot water production can be switched off. 

Start

 

and 

Stop date

Room temperature

 and 

Block hot water production

 are 

only displayed if the holiday function is activated.

3.1 Circuit 1 and hot water

3.1.1 Activate holiday function

3.1.2 Start date

3.1.3 Stop date

▶ Set start and stop date for the desired period. Format yyyy-mm-dd.

The period starts and ends at 00:00. Both the start and end date are 
included in the period.

▶ Terminate the period prematurely by indicating 

No

  in menu item 

3.1.1

 

Activate holiday function

 .

3.1.4 Room temperature

▶ Set the room temperature that should apply to the circuit during the 

period. 

3.1.5 Copy to all heating circuits

3.1.6 Block hot water production

3.2

 

Circuit 2

  (option)

▶ Set the values in the same way as for 

3.1

 

Circuit 1 and hot water

 .

3.3

 

Circuit 3

  (option)

▶ Set the values in the same way as for 

3.1

 

Circuit 1 and hot water

 .

3.4

 

Circuit 4

  (option)

▶ Set the values in the same way as for 

3.1

 

Circuit 1 and hot water

 .

6.5

Energy measurements

6.1 Generated energy

This displays 

6.1 Generated energy

  in kWh divided into 

6.1.1

 

Heating

 

and 

6.1.3 Hot water

.

6.2 Consumption electric additional heat

This displays 

6.2 Consumption electric additional heat

 in kWh divided 

into 

6.2.1 Heating

  and 

6.2.2 Hot water

 .

6.6

Timers

Timers are used by the control unit to count down the different time 
dependent functions such as 

Extra hot water duration

. At customer 

level the following timers can be observed (only timers that are counting 
are displayed):

6.7

External control

When an external input is connected, the control unit performs functions 
which are set to 

Yes

 or is separated from 0 (

Room temperature

). When 

the external input is no longer connected, the control unit returns to 
normal mode. Only installed functions are displayed.

8.1 Heat pump 1

 

8.1.1 External input 1

 

8.1.1.9 Block compressor

 

8.1.1.11 Block additional heat

 

8.1.1.12 Block heating at tripped underfloor temperature limiter

 

8.1.1.13 Block heating

 

8.1.1.14 Room temperature

 

▶ Set the room temperature that should apply in the event of enabled 

external control.

▶ Value > 0 °C enables the function.

The highest temperature is used if temperature changes have been set 
for a certain circuit at several external inputs.

8.1.1.15 Block hot water production

 

8.1.2 External input 2

 

▶ Set the values in the same way as for 

8.1.1

 

External input 1

 .

8.2 Heat pump 2

 

▶ Set the values in the same way as for 

8.1

 

Heat pump 1

 .

8.5 External input circuit 2

 

8.5.2 Block heating at tripped underfloor temperature limiter

 

8.5.3 Block heating

 

8.5.6 Room temperature

 

8.6 External input circuit 3

 

▶ Set the values in the same way as for 

8.5

 

External input circuit 2

 .

8.7 External input circuit 4

 

▶ Set the values in the same way as for 

8.5

 

External input circuit 2

 .

6.8

General

Among other things, settings for date and time are available here. 

12.1 Room sensor settings

12.1.1 Show outdoor temperature in room sensor

12.2 Set date

12.3 Set time

▶ Check and change, if necessary, date and time. These are used by the 

control unit to manage the different clock settings, e.g., holiday and 
room temperature program.

12.4 Summer/winter time

▶ Select if there should be automatic change over between summer 

and winter time or not (dates according to EU standard).

12.6 Display contrast

▶ If necessary, change the background light of the control panel.

12.7 Language

▶ Change language, if desired.

6.9

Alarms

The different alarms that can occur are described in (

Chapter 7).

Under 

13

 

Alarms

  there is:

13.1 Information log

13.2 Delete information log

13.3 Alarm log

13.4 Delete alarm log

13.7 Alarm indication

13.1 Information log

Energy is measured per compressor; the calculated 
results are added prior to being displayed.

Timer

F value

7.1 Extra hot water 

0h

7.3 Alarm mode delay 

1h

7.5 Operating time for heating at hot water demand 

20min

7.6 Hot water, operating time at heating demand 

30min

7.7/7.8 Heat pump x timers 

7.7.1/7.8.1 Compressor start delay 

10min

7.11 Additional heat timers 

7.11.1 Additional heat start delay 

60min

7.11.2 Delay mixing valve control after additional heat start 

20min

Table 8 Timers

Summary of Contents for Rego 1000

Page 1: ...User Guide Rego 1000 mode info menu ok 6 721 831 662 2021 03 en ...

Page 2: ...n in the menu display 5 4 Information from the heat pump 5 4 1 Operating information 5 4 2 Info button 6 4 3 Operating symbols 6 5 Menu overview 7 6 Settings Customer level 8 6 1 Mode button functions 8 6 2 Room temperature 9 6 3 Hot water 12 6 4 Holiday 13 6 5 Energy measurements 13 6 6 Timers 13 6 7 External control 13 6 8 General 13 6 9 Alarms 13 6 10 Access level 14 6 11 Return to factory sett...

Page 3: ...on in savings Only use original spare parts Service and maintenance must be carried out annually by an authorised service representative Safety of electrical devices for domestic use and similar purposes The following requirements apply in accordance with EN 60335 1 in order to prevent hazards from occurring when using electrical appliances This appliance can be used bychildren of 8 years and olde...

Page 4: ... version etc 3 Menu navigation 3 1 Initial menu Initial menu shows different temperatures time as well as current operating symbols The window displays information alternately Room temperature if room sensors exist and Flow temperature for each circuit installed Fig 2 Initial menu 1 Outdoor temperature 2 Current operating symbols 3 The circuit room temperature 4 Current time 5 Hot water temperatur...

Page 5: ...how that the next level is a setting window 5 The function is marked 6 Three of the functions under Hot water Fig 12 Help information 2 1 Graphic display of the value 2 Highest possible value 3 Unit 4 Previous value 5 New value Saved when the menu dial is pressed 6 Lowest possible value Fig 13 Help information 3 1 Option 4 out of 9 is displayed 4 Information from the heat pump The heat pump provid...

Page 6: ...mponents for which there is a need or which are in operation are displayed in the bottom right corner oftheInitialmenu Theoperatingsymbolsdisplayedcanvarydepending on the type of heat pump Fig 16 Operating symbols 1 Compressor 2 Alarm compressor additional heat 3 Heating 4 Electric additional heat 5 Energy supply cut off 6 Hot water 7 Extra hot water 8 Hot water peak 9 Pool option 10 Cooling optio...

Page 7: ...1 1 11 8 Copy to all heating circuits No No Yes 1 3 Circuit 2 option 1 3 5 Heat curve see 1 1 5 1 3 7 Room sensor see 1 1 10 1 3 8 Room temperature program see 1 1 11 1 4 Circuit 3 option see 1 3 1 5 Circuit 4 option see 1 3 1 10 General 1 10 1 Summer winter operation 1 10 1 1 Winter operation Automatic On Automatic Off 1 10 1 2 Outdoor temperature limit for change over 18 C 5 C 35 C 2 Hot water 2...

Page 8: ...ing at tripped underfloor temperature limiter No No Yes 8 5 3 Block heating No No Yes 8 5 6 Room temperature No 0 0 C 10 0 C 35 0 C 8 6 External input circuit 3 option see 8 5 8 7 External input circuit 4 option see 8 5 12 General 12 1 Room sensor settings 12 1 1 Show outdoor temperature in room sensor No No Yes 12 2 Set date yyyy mm dd 12 3 Set time hh mm ss 12 4 Summer winter time Automatic Manu...

Page 9: ...or T1 for circuit 2 full name E12 T1 Each circuit is controlled by its own heat curve The installer sets the typeofheatingforeachcircuit thatisRadiatororUnderfloor Theheat curveforUnderfloorhaslowervaluesbecausethefloorsdonottolerate such high temperatures Fig 17 Radiator The figure indicates the factory setting curve for a radiator circuit At 2 5 C the flow set point is 37 4 C Fig 18 Underfloor T...

Page 10: ... leave the curve setting window and return to the menu 1 1 6 Compressor 1 operating time on off Select how long the compressor should be on or off in heating mode Higher set values result in fewer compressor starts and stops which achieves higher economy However more pronounced temperature fluctuations in the heating system may result than with lower values 1 1 7 Compressor 2 operating time on off...

Page 11: ... Use this function to adjust the room temperature so that the normal room temperature see the previous menu becomes the desired temperature Use this function to simply increase or decrease the heat when there are no room sensors Results in approx 1 C lower room temperature results in approx 0 5 C lower room temperature results in approx 0 5 C higher room temperature results in approx 1 C higher ro...

Page 12: ...ghtly lower temperature Change to Comfort If more or hotter hot water is desired Thissettingmustbeusedifelectricadditionalheatismissingorifthe hot water circulation is used when the temperature in the hot water circulation is otherwise too low The factory settings for on and off temperature are approx 8 K C lower in Economy mode compared to Comfort mode These values can be adjusted by the installe...

Page 13: ...ock heating at tripped underfloor temperature limiter 8 1 1 13 Block heating 8 1 1 14 Room temperature Set the room temperature that should apply in the event of enabled external control Value 0 C enables the function The highest temperature is used if temperature changes have been set for a certain circuit at several external inputs 8 1 1 15 Block hot water production 8 1 2 External input 2 Set t...

Page 14: ...olunitisusedtoshowON OFFstatusforthe heatpumpbutalsotoshowpossiblealarms Thestatuslampistherefore also called alarm lamp Intheeventofanalarmthealarmlampflashesred controlunit untilthe warning cause has disappeared The alarm lamp is not used for warning alarms The room sensor alarm lamp can be blocked The room sensor display is used to indicate alarms for some alarm categories 10 The display window...

Page 15: ...gory A Alarm lamp buzzer Yes Restart Acknowledgement is required Contact the dealer if the alarm remains active for more than three hours or recurs often 7 7 2 Tripped low pressure switch E2x RLP Function Compressor stops Activated when the pressure in the refrigerant circuit of the heat pump becomes too low Alarm timer starts Yes Reset condition The pressure goes back to the permitted level Categ...

Page 16: ...ailure on sensor E2x T6 hot gas Function The compressor stops because the hot gas cut out cannot be guaranteed Activated when the sensor s value indicates a temperature lower than 50 C Alarm timer starts Yes Reset condition The value of the sensor indicates 50 C Category E Alarm lamp buzzer Yes Restart Automatic once the alarm cause has disappeared Contact the dealer if the alarm remains active fo...

Page 17: ...ent is required Contact the dealer 7 7 19 Failure on sensor E11 T1 flow Function The system switches over to control based on sensor T8 The alarmisactivatedwhenthesensor svalueindicatesatemperaturelower than 0 C Reset condition The value of the sensor indicates 0 C Category H Alarm lamp buzzer Yes Restart Automatic once the alarm cause has disappeared Contact the dealer if the alarm remains active...

Page 18: ... recurs often 7 7 29 Failure on sensor E31 TT T5 room Function The alarm is activated when the sensor s value indicates a temperature lower than 1 C In the event of a failure on sensor T5 the room temperature influence is set to 0 Reset condition The value of the sensor indicates 1 C Category H Alarm lamp buzzer Yes Restart Automatic once the alarm cause has disappeared 7 7 30 Short circuit on sen...

Page 19: ...at transfer fluid out and heat transfer fluid in becomes too high Reset condition The warning is deactivated on acknowledgement of the warning display Category L Alarm lamp buzzer No Restart The warning does not close anything but is registered in the alarm log Check and clean the particle filter if required Contact the dealer if the warning remains after acknowledgement 7 8 3 High temperature dif...

Page 20: ... condition The temperature of the collector circuit exceeds the lowest permitted temperature Category J that can be transformed into A 7 9 6 Hot water peak failure new try within 24 hours Function The hot water has not come up at the right temperature The hot water peak is repeated at the same time on the next day Reset condition The correct hot water peak temperature is reached Category Z 7 9 7 T...

Page 21: ...Rego 1000 6 721 831 662 2021 03 en 21 Notes ...

Page 22: ...Rego 1000 6 721 831 662 2021 03 en 22 Notes ...

Page 23: ...Rego 1000 6 721 831 662 2021 03 en 23 Notes ...

Page 24: ......

Reviews: