Settings Customer level
Rego 1000 – 6 721 831 662 (2021/03) en
13
6.4
Holiday
During holidays (absence), the heating can, for example, be kept at a
lower or higher level and hot water production can be switched off.
Start
and
Stop date
,
Room temperature
and
Block hot water production
are
only displayed if the holiday function is activated.
3.1 Circuit 1 and hot water
3.1.1 Activate holiday function
3.1.2 Start date
3.1.3 Stop date
▶ Set start and stop date for the desired period. Format yyyy-mm-dd.
The period starts and ends at 00:00. Both the start and end date are
included in the period.
▶ Terminate the period prematurely by indicating
No
in menu item
3.1.1
Activate holiday function
.
3.1.4 Room temperature
▶ Set the room temperature that should apply to the circuit during the
period.
3.1.5 Copy to all heating circuits
3.1.6 Block hot water production
3.2
Circuit 2
(option)
▶ Set the values in the same way as for
3.1
Circuit 1 and hot water
.
3.3
Circuit 3
(option)
▶ Set the values in the same way as for
3.1
Circuit 1 and hot water
.
3.4
Circuit 4
(option)
▶ Set the values in the same way as for
3.1
Circuit 1 and hot water
.
6.5
Energy measurements
6.1 Generated energy
This displays
6.1 Generated energy
in kWh divided into
6.1.1
Heating
and
6.1.3 Hot water
.
6.2 Consumption electric additional heat
This displays
6.2 Consumption electric additional heat
in kWh divided
into
6.2.1 Heating
and
6.2.2 Hot water
.
6.6
Timers
Timers are used by the control unit to count down the different time
dependent functions such as
Extra hot water duration
. At customer
level the following timers can be observed (only timers that are counting
are displayed):
6.7
External control
When an external input is connected, the control unit performs functions
which are set to
Yes
or is separated from 0 (
Room temperature
). When
the external input is no longer connected, the control unit returns to
normal mode. Only installed functions are displayed.
8.1 Heat pump 1
8.1.1 External input 1
8.1.1.9 Block compressor
8.1.1.11 Block additional heat
8.1.1.12 Block heating at tripped underfloor temperature limiter
8.1.1.13 Block heating
8.1.1.14 Room temperature
▶ Set the room temperature that should apply in the event of enabled
external control.
▶ Value > 0 °C enables the function.
The highest temperature is used if temperature changes have been set
for a certain circuit at several external inputs.
8.1.1.15 Block hot water production
8.1.2 External input 2
▶ Set the values in the same way as for
8.1.1
External input 1
.
8.2 Heat pump 2
▶ Set the values in the same way as for
8.1
Heat pump 1
.
8.5 External input circuit 2
8.5.2 Block heating at tripped underfloor temperature limiter
8.5.3 Block heating
8.5.6 Room temperature
8.6 External input circuit 3
▶ Set the values in the same way as for
8.5
External input circuit 2
.
8.7 External input circuit 4
▶ Set the values in the same way as for
8.5
External input circuit 2
.
6.8
General
Among other things, settings for date and time are available here.
12.1 Room sensor settings
12.1.1 Show outdoor temperature in room sensor
12.2 Set date
12.3 Set time
▶ Check and change, if necessary, date and time. These are used by the
control unit to manage the different clock settings, e.g., holiday and
room temperature program.
12.4 Summer/winter time
▶ Select if there should be automatic change over between summer
and winter time or not (dates according to EU standard).
12.6 Display contrast
▶ If necessary, change the background light of the control panel.
12.7 Language
▶ Change language, if desired.
6.9
Alarms
The different alarms that can occur are described in (
Chapter 7).
Under
13
Alarms
there is:
•
13.1 Information log
•
13.2 Delete information log
•
13.3 Alarm log
•
13.4 Delete alarm log
•
13.7 Alarm indication
13.1 Information log
Energy is measured per compressor; the calculated
results are added prior to being displayed.
Timer
F value
7.1 Extra hot water
0h
7.3 Alarm mode delay
1h
7.5 Operating time for heating at hot water demand
20min
7.6 Hot water, operating time at heating demand
30min
7.7/7.8 Heat pump x timers
7.7.1/7.8.1 Compressor start delay
10min
7.11 Additional heat timers
7.11.1 Additional heat start delay
60min
7.11.2 Delay mixing valve control after additional heat start
20min
Table 8 Timers