Rego 1000 – 6 721 831 662 (2021/03) en
18
Alarm
Reset condition:
The value of the sensor indicates
< 70 °C.
Category:
H.
Alarm lamp/buzzer:
Yes.
Restart:
Automatic once the alarm cause has disappeared.
▶ Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.25
Failure on sensor T3 hot water
Function:
The hot water production is terminated. The alarm is
activated when the sensor's value indicates a temperature lower than
0 °C.
Reset condition:
The value of the sensor indicates >0 °C.
Category:
H.
Alarm lamp/buzzer:
Yes.
Restart:
Automatic once the alarm cause has disappeared.
▶ Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.26
Short circuit on sensor T3 hot water
Function:
The hot water production is terminated. The alarm is
activated when the sensor's value indicates a temperature higher than
+110 °C.
Reset condition:
The value of the sensor indicates < 110 °C.
Category:
H.
Alarm lamp/buzzer:
Yes.
Restart:
Automatic once the alarm cause has disappeared.
▶ Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.27
Failure on sensor E1x.TT.T5 room
Function:
The room temperature influence is set to 0, which means that
the room sensor cannot affect the heating system any longer. The alarm
is activated when the sensor's value indicates a temperature lower than
-1 °C.
Reset condition:
The value of the sensor indicates
> -1 °C.
Category:
H.
Alarm lamp/buzzer:
Yes.
Restart:
Automatic once the alarm cause has disappeared.
▶ Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.28
Short circuit on sensor E1x.TT.T5 room
Function:
The room temperature influence is set to 0, which means that
the room sensor cannot affect the heating system any longer. The alarm
is activated when the sensor's value indicates a temperature higher than
+70 °C.
Reset condition:
The value of the sensor indicates
< 70 °C.
Category:
H.
Alarm lamp/buzzer:
Yes.
Restart:
Automatic once the alarm cause has disappeared.
▶ Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.29
Failure on sensor E31.TT.T5 room
Function:
The alarm is activated when the sensor's value indicates a
temperature lower than -1 °C. In the event of a failure on sensor T5, the
room temperature influence is set to 0.
Reset condition:
The value of the sensor indicates
> -1 °C.
Category:
H.
Alarm lamp/buzzer:
Yes.
Restart:
Automatic once the alarm cause has disappeared.
7.7.30
Short circuit on sensor E31.TT.T5 room
Function:
The alarm is activated when the sensor's value indicates a
temperature higher than +70 °C. In the event of a short circuit on sensor
T5, the room temperature influence is set to 0.
Reset condition:
The value of the sensor indicates
< 70 °C.
Category:
H.
Alarm lamp/buzzer:
Yes.
Restart:
Automatic once the alarm cause has disappeared.
7.7.31
Failure on sensor E2x.T8 heat transfer fluid out
Function:
Activated when the sensor's value indicates a temperature
lower than 0 °C.
Reset condition:
The value of the sensor indicates >0 °C.
Category:
H.
Alarm lamp/buzzer:
Yes.
Restart:
Automatic once the alarm cause has disappeared.
▶ Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.32
Short circuit on sensor E2x.T8 heat transfer fluid out
Function:
Activated when the sensor's value indicates a temperature
higher than 110 °C.
Reset condition:
The value of the sensor indicates
< 110 °C.
Category:
H.
Alarm lamp/buzzer:
Yes.
Restart:
Automatic once the alarm cause has disappeared.
▶ Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.33
Failure on sensor E2x.T9 heat transfer fluid in
Function:
Activated when the sensor's value indicates a temperature
lower than 0 °C.
Reset condition:
The value of the sensor indicates >0 °C.
Category:
H.
Alarm lamp/buzzer:
Yes.
Restart:
Automatic once the alarm cause has disappeared.
▶ Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.34
Short circuit on sensor E2x.T9 heat transfer fluid in
Function:
Activated when the sensor's value indicates a temperature
higher than 110 °C.
Reset condition:
The value of the sensor indicates
< 110 °C.
Category:
H.
Alarm lamp/buzzer:
Yes.
Restart:
Automatic once the alarm cause has disappeared.
▶ Contact the dealer if the alarm remains active for more than three
hours or recurs often.