English 6
When the regulator is securely installed on the manifold
pipe, the conversion nut will be easily accessible.
CAUTION:
Do not attempt any adjustment of the pressure
regulator, except conversion to propane.
Connect the gas supply line to the unit pressure regulator
using a 1/2" flex gas line connector between manual shut-
off valve and pressure regulator. Always use a new flex
line.
Check supply line connections for leaks using a soap
solution. Do not use a flame of any sort.
1. Turn on gas.
2. Apply a non-corrosive leak detection fluid to all joints
and fittings in the gas connection between the shut-off
valve and the range. Include gas fittings and joints in
the range if connections may have been disturbed
during installation. Bubbles appearing around fittings
and connections indicate a leak.
3. If a leak appears, turn off supply line gas shut-off valve
and tighten connections.
4. Retest for leaks by turning on the supply line gas shut-
off valve. When leak check is complete (no bubbles
appear), test is complete.
5. Wipe off all detection fluid residue.
Important Notes for Gas Connection:
•
The appliance and its individual gas shutoff valve must
be disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures in excess of 1/2 psig (3.5kPa).
•
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than 1/
2 psi (3.5kPa).
Connect Electrical Supply
Before connecting the 5-foot (1.5 m) supply cord to wall
receptacle, make certain that gas shutoff valve and all
burner controls are in OFF position.
Burner Cap Placement
WARNING:
To prevent flare-ups, do not use the cooktop
without all burner caps and all burner grates
properly positioned.
WARNING:
To prevent burns, do not touch burner caps or
grates while hot. Turn the cooktop off and allow
the burners to cool.
The burner caps must be properly placed for the cooktop to
function properly. If the burner cap is not properly placed,
one or more of the following problems may occur:
•
Burner flames are too high.
•
Flames shoot out of burners.
•
Burners do not ignite.
•
Burner flames light unevenly.
•
Burner emits gas odor.
Placing Burner Caps
Each cap has a letter (A, D, or F) cast in the underside of
the cap that corresponds to a letter (A, D, or F) cast in the
burner base that is attached to the appliance.
•
After electrical connection is complete, place each
burner cap on its correct burner base per its
Figure 7: Pressure Regulator
Figure 8: Gas and Electrical Location
1/2”
Female Pipe
Threads
Receptacle
Supply Cord
120 V
C of Wall
L
Flex Gas Line
Rough-in Box
Pressure
Regulator
Shows
Direction of
Gas Flow
Gas Shut-Off Valve
Cabinet Floor
Gas Stubout