MIYN46 Wall Transmitter
Installation | en
15
Bosch Security Systems
User Manual US
970.035b | F.01U.278.521 | v2.0 | 2012.12
4.3
Inputs and Outputs
4.4
General inputs
The * marks a factory setting.
4.5
Wired Outputs
4.6
Wired Inputs
External trigger J4
Jack
J1
NO*
Closing contact causes a Call for Help
NC
Contact opening causes a Call for Help
Power supply
J5
1
+
12 to 24 V DC
2
-
GND 0V
Call for Help
Relay
J5
3-4
B1
NO*
A Call for Help causes the closing of
the relay contact
NC
A Call for Help causes the opening of
the relay contact
Staff Presence
Relay
J5
5-6
B2
NO*
Staff Presence signaling causes the
closing of the relay
NC
Staff Presence signaling causes the
opening of the relay
Call for Help
J6
1-2
The contact closing causes a Call for
Help.
Technical
Alarm
J6
3-4
J2
NO*
The contact closing causes a Technical
Alarm
NC
The contact opening causes a Techni-
cal Alarm
Reserve Call or
Call for Assis-
tance
J6
4-5
J3
NO*
The contact closing causes a Reserve
Call or a Call for Assistance
NC
The contact opening causes a Reserve
Call or a Call for Assistance