background image

MDCI Series – All DC Inverter Outdoor Units (Three phase) 

6 720 862 442 (2016/04)

NORMAL OPERATION OF UNIT  |  7

6.  NORMAL OPERATION OF UNIT

Symptom 1:  The system does not operate

 

The air conditioning unit does not start immediately after the unit has 
been turned on. To prevent compressor overload the unit will start 
after 5 minutes.

 

If the operation lamp and the “pre def indicator or fan only indicator 
lights, it means you have chosen heat mode. When turned on if 
“anti cold wind” protection appears, it means the outside ambient 
temperature is too low and outside its parameters.

Symptom 2:  Changing to fan mode during cooling 

mode

 

Once the indoor unit has achieved it’s desired temperature, the 
unit will automatically switch to fan mode and circulate air. (This 
is to prevent the indoor unit frosting) When the temperature rises 
above the desired set point, the unit will automatically switch back 
to cooling mode.

Symptom 3:  White mist comes out of a unit

Symptom 3.1: Indoor unit

 

When humidity is high during cooling mode, the indoor unit can 
become contaminated and dirty. Ensure the indoor unit gets cleaned 
by a qualified personnel. This operation requires qualified personnel.

Symptom 3.2: Indoor unit, outdoor unit

 

When the system has changed over to heating after defrosting mode, 
moisture generated turns to steam and is exhausted.

Symptom 4:  Noises on the air conditioning unit 

Symptom 4.1: Indoor unit

 

When the unit is running, a low humming noise will be apparent until 
the unit has stopped.
When the drain pump (optional accessories) is in operation, a noise 
will be heard.
When the system stops after heating, the system will encounter a 
noise whilst the refrigerant settles down. Expansion valves shut down 
and refrigerant gets trapped in the system. 

Symptom 4.2: Indoor unit, outdoor unit 

 

A continuous low hissing sound is heard when the system is in 
operation.
This is the sound of refrigerant gas flowing through both indoor and 
outdoor units. 
A ‘hissing’ sound will be apparent when the unit starts and stops.
This is the noise of refrigerant.

Symptom 4.3: Outdoor unit

 

When the tone of the operating noise changes. 
This noise is caused by the change of frequency.

Symptom 5:  Dust comes out of the unit

When the system is not used for long periods, you may find dust that 
has settled in the unit discharges first.

Symptom 6:  The units can give off odours

 

Household smells can adhere to the units, cleaning the filters during 
service will improve this.

Symptom 7:  The outdoor unit fan does not spin

 

During operation. The speed of the fan is controlled in order to 
optimise product operation. 

7.  TROUBLESHOOTING

7.1  Problems and causes of the air conditioning 

unit

If one of the following malfunctions occur, stop operation, shut off the 

power, and contact with your dealer.

 

Should the light still flash when the unit has been powered off/on.

 

If the remote controller has faulted.

 

A safety device such as a fuse or a breaker frequently activates.

 

Should objects or water enter the unit.

 

Water leaks from indoor unit.

 

Other malfunctions.

If the system is not operating correctly and there are non of the above 

symptoms, then refer to table (7-1).

Summary of Contents for MDCI20-3

Page 1: ...ur air conditioning unit please read this manual carefully and keep it for future reference 6 720 862 442 2016 04 User manual CLIMATE 5000 VRF MDCISeries AllDCInverterOutdoorUnits Threephase MDCI20 3 MDCI22 3 MDCI26 3 ...

Page 2: ... Refrigerant pipework connector 4 Connection pipework Fig 1 NOTE All the pictures in this manual are for explanation purposes only They may be slightly different from the air conditioning unit you have purchased dependent on model Indoor unit Outdoor unit ...

Page 3: ...tect the heat exchanger When the unit is running fans will be operating Keep hands away from fan blades to prevent injury Ensure cleaning products do not come into contact with any of the units electrical components Caution should also be taken when using any other flammable or corrosive products close to the unit Never put any objects into the air inlet or outlet Objects touching the fan at high ...

Page 4: ...ESCRIPTION OF UNIT The air conditioning system consists of an outdoor unit indoor units connective pipework and a way of controlling the system remote controller see Fig 1 Force Cooling Control Force cooling control Button sw1 Display control button sw2 MAIN BOARD OUTDOOR UNIT sw1 sw2 Force Cooling Control Fig 2 1 Force cooling control of the outdoor unit is to be pressed when test running The uni...

Page 5: ... via the protection device until the problem has been solved 4 2 Electrical power to the unit is interrupted Shouldtheelectricalpowersupplybeinterrupted alloperationofthe unit will stop Isolate the main electrical supply to the unit until the electrical power supply has returned and stabilised When the electrical power supply is re established the controller will flash and will begin to initialise...

Page 6: ... do not match Irrecoverable HF 8 Reserved Recoverable E1 9 Communication fault between the outdoor and indoor units Recoverable E2 10 T3 T4 temperature sensor fault Recoverable E4 11 Voltage protection fault or a lack of Phase B Phase N Recoverable E5 12 DC fan motor fault Recoverable E6 13 Discharge temperature sensor fault Recoverable E7 14 A fan in the A region run for more than 5 minutes in he...

Page 7: ... until the unit has stopped When the drain pump optional accessories is in operation a noise will be heard When the system stops after heating the system will encounter a noise whilst the refrigerant settles down Expansion valves shut down and refrigerant gets trapped in the system Symptom 4 2 Indoor unit outdoor unit A continuous low hissing sound is heard when the system is in operation This is ...

Page 8: ...rrect refrigerant pressure Vacuum and recharge refrigerant Maintenance or change compressor Install manostat A qualified person should investigate Low cooling effect Outdoor unit and indoor unit heat exchangers are dirty The air filter is dirty Inlet outlet of indoor outdoor units is blocked Doors and windows are open Direct sunshine on outdoor unit Too much heat resource Outdoor temp is too high ...

Page 9: ...ler need changing The power supply is off The TEMP indicator does not come on Check whether the MODE indicated on the display is FAN ONLY The temperature cannot be set during FAN mode The indication on the display disappears after of time Check whether the timer operation has come to an end and TIMER OFF is not indicated on the display The air conditioning unit operation will stop at it s set time...

Page 10: ...6 720 862 442 2016 04 MDCI Series All DC Inverter Outdoor Units Three phase NOTES 10 ...

Page 11: ...MDCI Series All DC Inverter Outdoor Units Three phase 6 720 862 442 2016 04 NOTES 11 ...

Page 12: ......

Reviews: