LSN Peripherals | LSN Magnetic Contacts | 351
MSE-LSN B Built-In
Magnetic Contact
Features
▶
LSN flush-mount magnetic contact
▶
VdS class B
▶
Head-on or parallel flush mounting
▶
LSN perimeter protection
Magnetic contacts are used for tear-off surveillance of
doors and windows.
Certifications and Approvals
Region
Certification
Europe
CE
MSE/MSA-LSN B/C
Germany
VdS
G 104502, B MSE/MSA-LSN B
Installation/Configuration Notes
Installation notes
•
Head-on or parallel flush mounting.
•
The magnet should be fixed in the bore.
•
Head-on installation in ferromagnetic materials is
possible with the EG1 flush-mount housing.
1
Contact
2
Magnet
Connecting LSN contacts
•
Each LSN contact is a physical LSN element (1 out of
127 possible per loop).
•
The length of LSN contact connection cables must be
included when planning the total line length of the LSN
loop, as LSN technology is incorporated in these
detectors.
•
Passive coupling elements for joining the connection
cables to the installation cable must be placed as close
as possible to the LSN contacts. The 1 m connection
cable with 2 m LSN cable length is included in the
calculation of the LSN cable length (LSN is carried into
the contacts and back out again).
•
Connector boxes (optional) are classified as installation
material.
Testing LSN contacts
•
Reed switch and microswitch functions can be checked
before installation by a high-Ohm multimeter or
continuity checker (for diode paths).
•
The resistance values are approximate values; a large
change in resistance is significant here.
1
Detector
2
High-Ohm multimeter
Contact open: approx. 3 megaohm
Contact closed: approx. 1 megaohm
Note
Only the intrusion contact can be checked in
this way. The tamper switch of the Class C
magnetic contact can be checked by the LSN
control panel or with the LSN testing device
(software version 3.x onward).
Parts Included
Type
Qty.
Component
MSE-LSN B
1
Built-in magnetic contact
incl. 4 m cable
Technical Specifications
Type of installation
Flush, head-on or parallel
Operating voltage
Max. 33 V_
Reed contacts
Normally open contact
Switch tolerance
≥ 10
7
Magnet
AlNiCo 500
Switch dimension:
Ø 8 mm x 30 mm
Magnet dimension:
Ø 8 mm x 30 mm
Axial installation distance:
≤ 15 mm
Installation distance with EG1
2 to 6 mm
Temperature range
-25 °C to 70 °C
Connection cable:
4 m, LiY(St) Y 4 x 0.14 mm
with screen, exterior Ø 3.2 mm
www.boschsecurity.com
Bosch Security Systems B.V.
6