Page 49 from 56
6-720-821-364 SM HP270
– 250 - 200 2016/12 en
Note:
In new software version, in case of E09, the electrical heater is automatically switched ON to ensure a
minimum of 40ºC in tank until technician intervention (even if appliance is in HP or combi). Always do reset to error
before start troubleshooting as e-heater cable could be energized if T top < 40ºC.
Failure in High Pressure Side:
Compressor in Operation > 30
min before lock out
Yes
No
High Pressure Switch /
compressor thermal protection
activation 12 times consecutively
Water flow through condenser
is as specified?
Ensure circulation pump is
in speed 1 and ensure
plate heat exchanger is
free of sediments / debris
Water shortage for more than
12 h ?
NTC sensor top out of
pocket?
Too much refrigerant ?
Check air presence and
purge hydraulic circuit in
module
No
Yes
Remove gas charge and
ensure system has +/- 400 gr
Yes
Correct position and
ensure enter +/- 30 cm
(until white sticker)
Ensure compressor resistance is ok (at
20ºC)
C
– R ≈ 5.84 Ω
C
– S ≈ 7.62 Ω
No continuity should be measured between
compressor terminal and chassis:
C
– chassis ≠ 0
R
– chassis ≠ 0
S
– chassis ≠ 0
Check Compressor
Before the E09 error after the 12 tentatives, the
frost symbol blinks in display during the waiting
time of 1 hour until next attempt to start