background image

6 720 817 281 (2017/05)

Greentherm 9800 SEO 160/199 | SECO 199

30 | Maintenance and service

Heat Exchanger

Inspect burner observation window for cracks or spillage of 
flue gases. Observe burner flames during heater operation. 
Flames should be steady and blue with no signs of 
yellowing. Yellow burner flames are an indication of 
improper combustion. Refer to Section 4.5.1 of this 
manual to verify the combustion air supply meets the 
manufacturer's specifications.

Pressure Relief

Manually open the pressure relief valve to ensure proper 
operation.

Inlet Water Filter

Verify the inlet water filter screen is clean and undamaged. 
The inlet water filter is located on the bottom of the 
appliance, to the right of the cold water inlet fitting. (See 
Fig.13, page 19). Close the installer supplied water shutoff 
valve and remove wireform spring clip from filter. Remove 
the filter, clean and or replace if damaged.

Descaling

In areas where the water supply has a high mineral content, 
the heat exchanger should be flushed with a descaling 
solution. Scale build up will shorten the life of the water 
heater and damage resulting from scale is not covered 
under warranty. Refer to section9.3 for detailed 
instructions on descaling the heat exchanger.

Condensate Siphon

Check for debris and clean if needed.

9.2

Winterizing for seasonal use

The water heater must not be installed in a location where it 
may be exposed to freezing temperatures. If the heater must be 
left in a space which is likely to experience freezing 
temperatures, all water must be drained from the heater. 
NOTE: Use of agents such as anti-freeze is not permitted and 
voids the warranty, as they may cause damage to the water 
heater's internal components.

1. Press ON/OFF switch on the water heater to turn OFF the 

heater and unplug power supply cord. The display should 
be blank.

2. Shut off gas supply to heater.
3. Shut off the water supply to the water heater using installer 

supplied shutoff valve.

4. Open hot water taps to drain and relieve pressure from the 

plumbing system. If water continues to flow after 5 
minutes, a crossover of the hot and cold water pipes is 
present and must be corrected before proceeding.

5. Disconnect the inlet and outlet water pipes from the water 

heater. Place a small bucket underneath the water heater 
to catch residual water remaining inside the water heater.

6. Using an air compressor, blow short bursts of air (100psi 

max) through the inlet water connection until there is no 
water present coming through the outlet water connection 
of the heater.

7. Empty condensate trap.
8. Reconnect water fittings, refill the condensate trap and 

return heater to service when danger of freezing has 
passed.

9.3

Mineral scale build-up

Periodic descaling may be necessary in areas with high mineral 
content in the water. Scale buildup in the heat exchanger may 
result in lower flow rates, error codes of AA, E3, E5 and boiling 
sounds in the heat exchanger.
A water softener is required if the water hardness exceeds 14 
grains/gal (200 mg/l) calcium carbonate. Damage to the water 
heater resulting from hard water/scale deposits will not be 
covered under warranty.

Descaling using a pump

▶ Disconnect the electrical supply from the water heater.
▶ Shut off the water supply to the water heater using 

(installer supplied) shutoff valve.

▶ Open hot water taps to drain and relieve pressure from the 

plumbing system.

▶ Drain water from the unit's heat exchanger by 

disconnecting inlet and outlet water connections from the 
heater.

▶ Connect a line (A) from the outlet of the circulating pump 

(installer supplied) to the inlet water fitting on the water 
heater (see fig. 27.)

▶ Using another line (B), connect the water outlet fitting on 

the water heater. Route the other end of this line into a 
descaling reservoir.

▶ Using a 3rd line (C) from the descaling reservoir, connect 

to the inlet side of circulating pump. Install a filter on the 
end of the line in the descaling reservoir.

▶ Make sure all connections are "water tight.".
▶ Fill bucket with descaling solution so both lines inside are 

submersed. We recommend a straight white vinegar 
solution. If using a commercial descalant, refer to 
manufacturer's instructions for proper dilution ratio.

▶ Operate the circulating pump.
▶ Make sure there are no leaks and the solution is flowing 

from the descaling reservoir through the heater and 
returning to the reservoir.

▶ Run the solution through the heater until the solution 

returning to the descaling reservoir comes out clear. 
(Changing to a fresh solution may be necessary during this 
process).

Summary of Contents for Greentherm 9800 SECO 199

Page 1: ...hismanual Forassistanceoradditionalinforma tion consult a qualified installer service agency or the gas supplier Upon completion of the installation these instructions should be handed to the user of the appliance for future reference What to do if you smell gas Turn off the gas shut off valve Open windows and door if smell detected inside the house Do not try to light any appliance Do not touch a...

Page 2: ...ply 25 7 2 Position of the fuses in control unit 26 8 Operating Instructions 27 8 1 Digital display description 27 8 2 For your safety read before operating your water heater 27 8 3 Switching the appliance on off 27 8 4 Temperature control 28 8 5 Programming the default setpoint temperature 29 9 Maintenance and service 29 9 1 Annual maintenance 29 9 2 Winterizing for seasonal use 30 9 3 Mineral sc...

Page 3: ...missioning Do not install this device in confined spaces Function To ensure that the water heater functions properly follow these installation and maintenance instructions Never close the blow off line of the pressure safety valve For safety reasons water may escape during heating If you smell gas Turn off the gas shut off valve Open windows and doors if detected inside the house Do not try to lig...

Page 4: ...e at the tap install a thermostatic DHW mixing valve Water heatedfor washingthe laundry dishes and for other cleaning purposes can cause scalding and permanent injuries Children elderly andhandicappedpersonsaremorelikely to be permanently injured by hot water Never leave such individuals in the tub or shower unattended under any circumstances Children must not be allowed to operate hot water fauce...

Page 5: ... plumbing inspector on how to correct this situation Do not plug the relief valve WARNING Personal Injury from toxic chemicals Toxic chemicals such as those used for boilertreatment shallnotbeintroduced into the potable water used for space heating WARNING Personal Injury from toxic chemicals A water heater which will be used to supply potable water shall not be connected to any heating system or ...

Page 6: ... pipes Note The freeze prevention kit is designed to provide protection for the water heater down to approximately 4 F for short term conditions only It will not protect the applianceinareaswherethetemperatureisroutinelyexpected to be below freezing Thefreezepreventionkitwillnotprotectplumbingoutsidethe appliance from freezing Precautions should be taken Accessories Bosch part Neutralizer Kit 7738...

Page 7: ...000 2 6 9 000 2 6 Temperature Control4 Residential models Selection range F C 100 1205 38 49 100 1205 38 49 Commercial models Selection range F C 100 180 38 82 Default temperature F C 120 49 120 49 Temperature stability6 F C 2 1 2 1 Gas Requirement Gas connection inches Peak load inlet gas pressure7 Propane water column 8 13 8 13 Natural Gas water column 3 5 10 5 3 5 10 5 Water Top hot water conne...

Page 8: ...flowarebaseduponsettingtheunittohighertemperaturesandthenmixingdownusingcoldwateraftertheunit toreach these flow rates 2 Input rating is based on sea level operation and need not be changed for operation up to 2000 ft 610 m elevation For operationatelevationsabove2000ft 610m inputratingisautomaticallyreducedattherateof4percent US or10percent Canada for each 1000 ft 305 m above sea level 3 When con...

Page 9: ... not approved or designed for Manufactured mobile homes boats or any mobile installation Modular homes are acceptable for installation Use above 10500 ft A S L altitude Applications where inlet water temperature is higher than 140 F 60 C for Residential appliances or 180 F 82 C for Commercial appliances In these applications a 3 way valve or thermostatic mixing valve must be installed before the a...

Page 10: ...manual gas shutoff valve not supplied with heater during any pressure testing at pressures in excess of Psig 3 5 kPa 5 Keepwaterheaterareaclearandfreefromcombustibles and flammable liquids Do not locate the heater over any material which might burn 6 Correctgaspressureiscriticalfortheproperoperation of this heater Gas piping must be sized to provide the required pressure at the maximum output of t...

Page 11: ...6 720 817 281 2017 05 Greentherm 9800 SEO 160 199 SECO 199 Appliance details 11 3 5 Dimensions and minimum installation clearances Fig 4 Dimensions ...

Page 12: ...side temperatures is below 32 F 0 C water pipes should be properly insulated to maintain water temperature and prevent freezing DANGER The water heater must be installed by a qualified installer in accordance with these instructions If improperly installed a hazardousconditionsuchas explosion or carbon monoxide poisoning could result Bosch Thermotechnology Corp is not responsible for improperly in...

Page 13: ...method of the mounting bracket will depend on the type of mounting surface Due to the varieties of building siding or surfacing the installer must decide on how best to support and level the heater on an outside wall It is recommended that horizontal or vertical support boards or plywood sheathing minimum first be attached to the wall surface The heater must be kept level on the wall surface Fig 6...

Page 14: ... The appliances are supplied having been set in the factory for the values shown on the rating plate For any other adjustments see chapter 9 4 6 1 Natural gas 4 6 2 Liquid propane gas after gas conversion If gas conversion is needed Natural Gas to Liquid propane gas see section 10 13 O2 O2 6720817281 21 1V The appliances must not be operated if the dynamic gas pressure is less than 3 5 WC or great...

Page 15: ... NFPA 54 In Canada The Installation must conform to CGA B149 INSTALLATION CODES and or local installation codes GAS CONNECTIONS Install a manual gas shut off valve on the gas supply line within easy reach of the appliance Install a union when connecting the gas supply Gas connection to the water heater is a NPT See chapter 6 1 1 for the minimum internal pipe diameter required Undersized flexible a...

Page 16: ...he Greentherm 9800 SEO SECO 199 Measure the length of the gas supply line from the building s gas main to the heater and use the section 6 1 1 and 6 1 2 page 17 or the gas line manufacturer s sizing tables to determine the pipe diameter necessary Iftherearemoregasdrawingappliancesontheline sizethegaslineaccordingtothetotalmaximumamountofBTU draw input rating of for all appliances combined Note Und...

Page 17: ...55 WC or 138 mbar and a pressure drop of 3 0 W C 7 5 mbar based on 0 60 specific gravity gas Maximum pipe capacity in cubic feet of Natural Gas per hour for gas pressures of 2 0 psig 55 WC or 138 mbar and a pressure drop of 3 0 W C 7 5 mbar based on 0 60 specific gravity gas EHD EquivalentHydraulicDiameter Thegreaterthevalueof EHD the greater the gas capacity of the tubing Initial Supply Pressure ...

Page 18: ...binginThousandsofBTU hrofUndilutedLiquefied Petroleum Gases at 11 inches Water Column Inlet Pressure Based on a Pressure Drop of 0 5 Inch Water Column Source National Fuel Gas Code NFPA 54 ANSI Z223 1 No Additional Allowance is necessary for an ordinary number of fittings Pipe Sizing Between Single or Second Stage Low Pressure Regulator and Appliance Nominal Iron Pipe inches Internal Diameter inch...

Page 19: ... are not suitable for connecting directly to or within an 18 pipe run of the water heater Although water piping throughout the building may be other than copper we recommend that copper or suitably rated stainless steel flex line be used for the water connections for 1 5 on either side of the water heater follow local codes if more stringent Description Max Levels pH pH 6 5 8 5 TDS total Dissolved...

Page 20: ...k the lowest pressure range setting recommended is 30 psi 2 06 bar Proper insulation material should be used in places prone to freezing conditions Connecting the pressure relief valve PRV A pressure relief valve must be installed at the time of installation No valve is to be placed between the PRV and the heater No reducing coupling or other restriction may be installed in the discharge line The ...

Page 21: ...Expansion tank field supplied 5 Circulator cable accessory 6 PRV 7 Shutoff valves field supplied 8 Greentherm 9800 SEO SECO Fig 16 Recirculation application using the cold water line and cross over valve 1 Cold water supply 2 Check valve field supplied 3 Circulator pump field supplied 4 Expansion tank field supplied 5 Circulator cable accessory 6 PRV 7 Shutoff valves field supplied 8 Greentherm 98...

Page 22: ...ating only applications closed loop setup Bosch supports applicationsofcombinationDHWandspaceheatinginanopen loop configuration if plumbed similar to fig 17 Please see warranty document for additional details CAUTION If the set point temperature is above 120 F precautions should be taken to protect users of potable water from scalding For external pump sizing please refer to the pressure drop curv...

Page 23: ...ank as required 7 Air purge field supplied 8 Cold water supply 9 Check valve field supplied 10 Thermostatic mixing valve field supplied 11 Thermometer optional field supplied 12 DHW outlet 13 Thermostat only valid if air handler includes a internal pump field supplied 14 Air handler 15 Shutoff valve 16 Circulation pump only required if air handler doesn t includes internal pump field supplied 17 C...

Page 24: ...6 720 817 281 2017 05 Greentherm 9800 SEO 160 199 SECO 199 24 Installation instructions Fig 18 Pressure drop curve ...

Page 25: ...en more hot water fixtures to allow sufficient flow and access to P1 Record the lowest operating gas pressure reading in table 12 Turn OFF the appliance Shut off gas supply Disconnect the manometer tube from the test point Tighten the screw inside test point fitting Gas pressures lower than 3 5 W C for Natural Gas or 8 W C for LPG may result in reduced power output Fig 19 Gas pressure test port 1 ...

Page 26: ... two phillips head screws securing the control unit Disconnect all the cables from the control unit Press the four snaps of the control unit and remove the cover Fig 21 Control Unit Pressthefour snaps inside thecontrolunitand remove the PCB Check the fuse on the printed circuit board for electrical continuity see fig 22 1 Fig 22 Fuse position 1 Fuse After checking the fuse reinstall all parts in r...

Page 27: ...ding and notify the police and fire department from outside the building From outside the building call the gas utility company and a trained and certified installer B Never use tools close the gas supply and call a qualified service technician Forceful repair may result in a fire or explosion C Do not use this appliance if any part has been under water Immediately call a qualified service technic...

Page 28: ...se of this type of temperature overshoot To combat this symptom clean fixtures or replace with higher flowing ones if necessary The water heater will not ignite if inlet water temperature exceeds the set point temperature minus 1 F 0 5 C In this condition the solar mode indicator will show on the display If the appliance does not ignite this means that the desired set temperature would be exceeded...

Page 29: ... flamesmaybean indication of poor ventilation or combustion air intake Inspect combustion air openings for blockage or debris DANGER Always shut off the electrical power supply shut off the manual gas valve and shut off the water valves whenever servicing DANGER Replacealldismantledjointsando rings with new ones 6720806146 05 1V NOTICE Inspect and clean the complete water heating system once a yea...

Page 30: ...ect the inlet and outlet water pipes from the water heater Place a small bucket underneath the water heater to catch residual water remaining inside the water heater 6 Using an air compressor blow short bursts of air 100psi max through the inlet water connection until there is no water present coming through the outlet water connection of the heater 7 Empty condensate trap 8 Reconnect water fittin...

Page 31: ...ually increase water flow hotwaterdemand throughtheheatertodetermineif the heater activates with higher flow 5 Cleantheinletwaterfilterscreenperchapter6 3 page19 6 Inspect the water path for obstructions Make sure all shower heads faucet aerators and whole house filters are clear of debris 7 Check fora plumbing crossover A crossoverin the hotand cold plumbing pipes creates back pressure on the wat...

Page 32: ...ectedtemperatureontheunitissettoohighforthe demanded flow rate the water heater will close its motorized water valve reducing the hot water flow rate in an attempt to reach the selected output temperature Loweringtheselectedtemperaturewillallowthemotorized water valve to open up for increased water flow rate 4 Cleantheinletwaterfilterscreenperchapter9 1 page29 5 Inspect the water path for obstruct...

Page 33: ...tment as described in section 10 11 10 9 Error codes EA and or EC EA and EC errors can appear if combustion is not properly set This could be caused by improper gas supply conditions gas pressure and or gas composition 1 Verify if correct gas type is selected see section 10 13 2 Verify is gas pressure is within specified range see section 3 2 Ifgastypeisproperlyselected gaspressureiswithinrange an...

Page 34: ...2 measuring port Use a properly calibrated CO2 analyzer when making the following adjustments 10 11 2Adjusting the maximum flow Parameter P1 Press the button to turn ON Press and hold simultaneously buttons and for 3 seconds until display reads P2 Fig 30 Press to enter P2 adjustment The current setting will appear on the display factory default Press or until P1 appears Turn on high volume of hot ...

Page 35: ...rts blinking as sign of confirmation Press button to finnish the L2 gas adjust U2 Press or until P2 appears Press the button Display with indication E Press the button until the display shows A2 Press The appliance is now in the position for adjustment of the maximum air flow Press the buttons or until the CO2 analyzer shows the value indicated in tab 17 Press the button for 3 seconds The value fl...

Page 36: ... SE SEC O 199 000 BTU Nat Gas max input P1 8 5 8 9 250 ppm min input P2 2 3 2 5 30 ppm LP Gas max input P1 9 8 10 2 250 ppm min input P2 2 8 3 0 30 ppm Values above are for climate controlled conditions Inputs such as gas pressure heating value of the gas humidity and temperature of combustion air all impact CO and CO2 values Changes in these inputs can result in different CO and CO2 values on the...

Page 37: ...djustments Access service mode by pressing and hold down at the same time and for 3 seconds Display with indication P2 Press buttons or until the display shows P7 Press Press buttons or and select the gas type according to table 19 Update TYPE OF GAS in the rating plate of the appliance using the label provided with the gas conversion kit After changing the type of gas proceed with the adjusting m...

Page 38: ... in the tank pocket Verify if correct recirculation settings are in use section 6 4 1 Replace the sensor and or wire connections if the problem persists 1 A3 Exhaust temperature sensor fault 15 Check sensor wire connections 1 2 Replace the sensor and or wire connections if the problem persists 1 A4 Air temperature sensor 18 disconnected or damaged Check sensor wire connections 1 2 Replace the sens...

Page 39: ...ion 10 11 1 C3 Flow sensor 14 does not detect water recirculation Check pump and connections 1 Check recirculation circuit for any blockage C5 Bypass water valve 8 disconnected or damaged Check bypass water valve wire connections 1 If the problem persists Replace the bypass water valve and or wire connections 1 C7 Fan 2 disconnected or damaged Check fan wire connections Reset error press and hold ...

Page 40: ... temperature instabilities E3 Flue gases temperature above 194 F or 2 minutes above 145 F Appliance burner cut off to prevent overheating Descale appliance section 9 3 1 Reset error press and hold on off button for 3 seconds If the problem persists Check sensor resistance 15 section 13 and replace the sensor if it is not according to specification 1 2 E4 Air temperature inside cabinet above 176 F ...

Page 41: ...ts Replace electronic control unit 1 F3 Electronic control unit internal error Reset error press and hold on off button for 3 seconds If the problem persists Replace electronic control unit 1 F7 Electronic control unit internal error Reset error press and hold on off button for 3 seconds If the problem persists Replace electronic control unit 1 F8 Electronic control unit internal error Reset error...

Page 42: ...gh pitch noise whistling Combustion flame with gas in excess or lack of air Check if gas type is correct section 3 3 1 Check gas inlet pressure section 6 6 1 Perform gas and air tuning section 10 11 1 Low pitch noise with vibration rumbling Combustion flame with air in excess or lack of gas Check if gas type is correct section 3 3 1 Check gas inlet pressure section 6 6 1 Perform gas and air tuning...

Page 43: ...6 720 817 281 2017 05 Greentherm 9800 SEO 160 199 SECO 199 Electrical diagram 43 12 Electrical diagram Fig 34 Electrical diagram ...

Page 44: ...er valve 9 Electrovalve 3 10 Electrovalve 1 11 Electrovalve 2 12 Gas valve safety solenoid 13 Thermal fuse 14 Water flow sensor 15 Flue dases temperature sensor 16 Condensing unit flue gases temperature sensor 17 Outlet hot water temperature sensor 18 Air temperature sensor 19 Heat exchanger hot water temperature sensor 20 Inlet cold water temperature sensor 21 External water temperature sensor Aq...

Page 45: ...Back flow and exhaust gas NTC characteristic 40 22 4 14 32 50 68 86 104 122 140 158 176 194 40 30 20 10 0 10 20 30 40 50 60 70 80 90 100 110 120 212 230 248 0 1 1 100 RESISTANCE KOHM TEMPERATURE ºF ºC 6720816948 40 1V 10 40 4 32 68 104 140 176 212 284 320 392 428 464 40 20 0 20 40 60 80 100 140 160 200 220 240 248 120 356 180 0 01 0 1 1 10 100 RESISTANCE KOHM TEMPERATURE ºF ºC 6720816948 41 1V ...

Page 46: ...am and parts list 14 Interior components diagram and parts list 14 1 Interior components Fig 37 Components 1 Air fan 2 Control unit 3 Gas manifold 4 Burner 5 Heat exchanger 6 Condensing unit 7 Water valve 8 By pass 9 Gas valve 10 Condensate trap 11 Ionization sensor 12 Ignition electrodes ...

Page 47: ...6 720 817 281 2017 05 Greentherm 9800 SEO 160 199 SECO 199 Interior components diagram and parts list 47 Fig 38 Appliance overview ...

Page 48: ...cled at the end of the productlife Contactyourcityauthoritiesforinformationabout the disposal of recyclable products Saving water resources Makesureyoucloseallthetapsafteranyuse Avoidleaving the taps dripping Repair any leaking tap Define the temperature you want in the appliance or with the remote control This way you have the precise water flow needed mixing cold water to regulate temperature wi...

Page 49: ...n the rating plate which is located on the right side of the appliance cabinet ___ ___ ___ ___ ___ ___ ___ ___ Gas Pressure Reading 2 2 See Chapter 6 6 page 25 and gas pressure table to be filled out by installer Static Dynamic Water Pressure Building Water Pressure Range if on Well system Installing Company Installer name Address Phone Table 21 Installation manual should be left with the owner af...

Page 50: ...6 720 817 281 2017 05 Greentherm 9800 SEO 160 199 SECO 199 50 Notes ...

Page 51: ...6 720 817 281 2017 05 Greentherm 9800 SEO 160 199 SECO 199 51 Notes ...

Page 52: ......

Reviews: