22
|
Information about the appliance
Greenstar
6 720 806 992 (2015/03)
3.15 Technical data heating boiler ZBR42-3A...
Input/Output at elevation 0 - 2000 feet (0 - 610 m)
Unit
NG
LPG (propane)
Max. input rate 180/79 °F (82/26 °C)
BTU/hr (kW)
151,600 (44.4)
148,300 (43.5)
Max. output rate 104/86 °F (40/30 °C)
BTU/hr (kW)
137,500 (40.3)
137,500 (40.3)
Max. output rate 122/86 °F (50/30 °C)
BTU/hr (kW)
137,500 (40.3)
137,500 (40.3)
Max. output rate 176/140 °F (80/60 °C)
BTU/hr (kW)
134,400 (39.4)
134,400 (39.4)
Min. input rate 180/79 °F (82/26 °C)
BTU/hr (kW)
36,000 (10.5)
46,400 (13.6)
Min. output rate 104/86 °F (40/30 °C)
BTU/hr (kW)
35,500 (10.4)
46,400 (13.6)
Min. output rate 122/86 °F (50/30 °C)
BTU/hr (kW)
35,100 (10.3)
46,100 (13.5)
Min. output rate 176/140 °F (80/60 °C)
BTU/hr (kW)
31,700 (9.3)
42,000 (12.3)
Input/Output at elevation 2000 - 4500 feet (611 - 1372 m) above sea level
Max. input rate 180/79 °F (82/26 °C)
BTU/hr (kW)
136,440 (40.0)
139,402 (40.9)
Max. output rate 104/86 °F (40/30 °C)
BTU/hr (kW)
123,750 (36.3)
129,250 (37.9)
Max. output rate 122/86 °F (50/30 °C)
BTU/hr (kW)
123,750 (36.3)
129,250 (37.9)
Max. output rate 176/140 °F (80/60 °C)
BTU/hr (kW)
120,960 (35.5)
126,336 (37.0)
Input/Output at elevation 4500 - 7000 feet (1373 - 2134 m) above sea level
Max. input rate 180/79 °F (82/26 °C)
BTU/hr (kW)
125,828 (36.9)
129,021 (37.8)
Max. output rate 104/86 °F (40/30 °C)
BTU/hr (kW)
114,125 (33.5)
119,625 (35.1)
Max. output rate 122/86 °F (50/30 °C)
BTU/hr (kW)
114,125 (33.5)
119,625 (35.1)
Max. output rate 176/140 °F (80/60 °C)
BTU/hr (kW)
111,552 (32.7)
116,928 (34.3)
Gas connection value
Natural Gas – H
s
= 1,010 BTU/ft
3
(37.3MJ/m
3
)
ft
3
/hr (m
3
/h)
149 (4.2)
–
Liquid Propane Gas – HD-S = 2,500 BTU/ft3 (93.1MJ/m3)
ft
3
/hr (m
3
/h)
–
59 (1.7)
Permissible inlet gas pressure
NG
in. W.C. (mbar)
3.5-10.5" (8.7-26.1)
–
LPG (propane)
in. W.C. (mbar)
–
8-13" (19.9-32.3)
Flue gas
Flue gas mass flow at maximum/minimum nominal output
gps
18.0/4.5
17.5/5.6
Flue gas temperature 176/140 °F (80/60 °C) at maximum/minimum nominal heat
input
°F ( °C)
171/135 (77/57)
171/135 (77/57)
Flue gas temperature 104/86 °F (40/30 °C) at maximum/minimum nominal heat
input
°F ( °C)
133/91 (56/33)
133/91 (56/33)
CO
2
at max. nominal output
%
9.4
11.0
CO
2
at minimum nominal output
%
8.6
10.4
Condensate
Max. condensate quantity (t
R
= 86 °F (30 °C))
gph (l/h)
0.9 (3.5)
0.9 (3.5)
pH level, approx.
4.8
4.8
General
Voltage
VAC
120
120
Frequency
Hz
60
60
Max. power consumption (central heating mode)
W
205
205
Max. power consumption (Stand-by)
W
< 6
< 6
Sound pressure level
dB(A)
45
45
Max. supply temperature
°F ( °C)
190 (88)
190 (88)
Max. permissible operating pressure (P
MS
) heating
psi (bar)
30 (2.07)
30 (2.07)
Permissible ambient temperature
°F ( °C)
32 - 122 (0 - 50)
32 - 122 (0 - 50)
Nominal water capacity (heating)
Gal (L)
0.925 (3.5)
0.925 (3.5)
Weight (without packaging)
lbs. (kg)
103.6 (47)
103.6 (47)
Dimensions, W x H x D
inch
(mm)
17-21/64" × 33-15/32" × 13-57/64"
(440 × 850 × 353)
Table 7 Technical data heating boiler ZBR42-3A...