COMPRESSOR REPLACEMENT
QV/WQ SERIES
3
8733829556 (2021/07) Subject to change without prior notice
Figure 4. Electrical Box Screws Location
5)
For Vertical Configuration only. Remove
compressor encapsulation screws that attach
the encapsulation to the divider (Qty 4).
Figure 5. Divider encapsulation screw locations
(Vertical unit configuration only)
6)
Cut pipes shown on figure 6 to remove
reversing valve assembly.
Figure 6. Suggested locations to cut pipes
7)
Remove Reversing valve assembly.
8)
Remove (and save to re-install later)
insulation pads around suction and discharge
pipes.
9)
Remove screws holding encapsulation panel
#3. See figure 7.
Figure 7. Encapsulation screw locations