108
en | Installation
Modular fire panel
07.2020 | 12.0 | F.01U.028.089
System Information
Bosch Sicherheitssysteme GmbH
Labeling
Connection
2
Ground
5
Door release magnet, +12 V/24 V, approx. 10 W
8
Key deposit lock monitoring
6 | 7
Ground
9
Heating, +24 V, approx. 8 W
10
Ground
FSE+ | −
FSE release element monitoring
⊗ + | −
Signal lamp, e.g. BEGA lamp +24 V, approx. 10 W
Relay 1-4
Information on the redundant connection of the module can be found in
The technical data can be found in
ENO 0000 B Fire Service Interface Module, page 151.
4.9.6
FPE‑5000‑UGM Interface Module
The FPE-5000-UGM Interface Module allows the stand alone fire panel or the panel network to
be connected to a higher-level system such as the UGM or to fire service devices such as FMF-
FAT/FMF-FBF-FAT. The module provides two bi-directional transmission paths.
The module has two LEDs per transmission path for indicating the status (green =
transmission, yellow = fault), and a key for testing the LEDs.
Figure 4.57:
FPE‑5000‑UGM Interface Module
Labeling
Connection
SDI 1 + | -
Transmission path 1
Data input + | -
SDO 1 + | -
Data | -
SDI 2 + | -
Transmission path 2
Data input + | -
SDO 2 + | -
Data | -
Information on the redundant connection of the module can be found in