Installation Instructions
Linear Smoke Detector Fireray 50/100RV
ST/PMF/zab
610- F.01U.002.706 / A2.en
Page 10 of 14
4.
Technical Data
Operating voltage
10 V DC
. . . 30 V DC
Current consumption:
- in standby mode
< 4 mA @ 24 V
- in standby mode
- in alarm/malfunction
< 4 mA @ 24 V
< 15 mA
Reset control by power disruption
> 5 s
Alarm relay
Normally open; dry
contact
(2 A @ 30 V DC)
Fault relay
Normally close; dry
contact
(2 A @ 30 V DC)
Permissible distance between Fireray and the
reflector:
- Fireray 50RV
- Fireray 100RV
5 m to 50 m
50 m to 100m
Optical wavelength
880 nm
Adjustable alarm threshold values
2.50 dB (25%)
3.74 dB (35%)
6.02 dB (55%)
Axial deviation tolerance
(at 35% sensitivity)
Detector
$
0.8
Prism reflector
$
5.0
Operating temperature
- 30
C . . . +55
C
Protection type
IP 50
Dimensions (W x H x D)
126 x 210 x 120 mm
Weight
670 g
Housing:
- Color
- Material
light gray/black
ABS, non - flammable
VdS ID number
G 203070
5.
Additional Documentation
For those with access authorization, on the Bosch ST ExtraNet at
www.boschbest.de
the current information for each product, as well as the installation instructions