PI - 34.85
Product Information Linear Smoke Detector Fireray 50/100RV
601-F.01U.002.705
A1.en / 29.12.2004
ST-FIR/ PRM1/ zab
Seite 19 von 22
10. Technical Data
Operating voltage
10 V DC
. . . 30 V DC
Current consumption:
in standby mode
< 4 mA @ 24 V
- in standby mode
- in alarm/malfunction
< 4 mA @ 24 V
< 15 mA
Reset control by power disruption
> 5 s
Alarm relay
Open contact, potential -
free
(2 A @ 30 V DC)
Fault relay
Break contact element,
potential - free
(2 A @ 30 V DC)
Permissible distance between the detector and the
prism reflector:
- Fireray 50R
- Fireray 100R
5 m to 50 m
50 m to 100m
Optical wavelength
880nm
Adjustable alarm threshold values
2.50 dB (25%)
3.74 dB (35%)
6.02 dB (55%)
Axial deviation tolerance
(at 35% sensitivity)
Detector
$
0.8
Prism reflector
$
5.0
Operating temperature
- 30
C . . . +55
C
Protection type
IP 50
Dimensions (W x H x D)
126 x 210 x 120 mm
Weight
670 g
Housing:
- Color
- Material
light gray/black
ABS, non - flammable
VdS ID number
G 203 070