PI - 34.85
Product Information Linear Smoke Detector Fireray 50/100RV
601-F.01U.002.705
A1.en / 29.12.2004
ST-FIR/ PRM1/ zab
Seite 13 von 22
7.4. Connection
(if voltage drop
<
6 V)
(if voltage drop
>
6 V)
UEB
UEA
SB
SA
1
2
3
1
2
3
1
LSN
- U
+U
- U
+U
1
Bridges Br1, Br2 in position 2-3
MALFUNCTION
ALARM
Power sup-
ply 10
-
30
V
Fireray 50/100 RV
rd
bl
R
E
NSB 100 LSN
I
3
I
4
NO
COM
NC
COM
NSB 100
EV 24 V - 24 V
I
1 NLT1
I
2
⊥
I
3 -U
Br 2
I
4 +U
II
1 NLT2
II
2
⊥
II
3 -U
II
4 +U
III
1
III
2
IV
1 RR
IV
2 R
V
1 KR
V
2 KA1
V
3 KA2
Br 1
VII
1
VII
2
VI
1
VI
2
ye
bl
gn
wh
2
2
Contacts in open position
Configuration for LSN:
Parameterize the NSB in the control panel to
control output KA1-KA2/KR-R-RR and
“Control with Fireray”.
Operating mode switches:
Prism Targeting
Alignment Mode
Operating Mode
DIP switch:
Functions, see table (below)
Output
for key switch
(optional)
Operating mode
switch
DIP switch
(recommended settings)
3K3
Connection of a Fireray 50/100RV using a NSB100 LSN at the fire panel
6 DA mini
distributor
on
off
-
+
680
Ω
*
DIP switch functions
DIP switch setting
*
DIP switch functions
1
2
3
4
50% threshold
X
X
OFF
OFF
35% threshold
X
X
OFF
ON
25% threshold
X
X
ON
OFF
Reserved for later use
X
X
ON
ON
X
Alarm relay saves the alarm
OFF
X
X
X
Automatic reset 5 s after the end of the alarm criterion
ON
X
X
X
Alarm relay after end of readjustment
X
OFF
X
X
X
Fault relay at end of readjustment, no alarm
X
ON
X
X
The factory presets are shaded in gray.
* The recommended settings for connection to a fire panel are marked with X.