background image

Ground 

The  UPM  controller  takes  its  ground 
reference  from  the  unit  chassis  which  is 
connected  to  the  controller  via  the  C-GND 
spade terminal. 

DIP Switch Settings 

The DIP switch is used to configure most of 
the available features of the UPM as follows: 

 

Alarm mode, Constant or Pulse 

 

Reset mode, Y signal or R signal 

 

Lockout  mode, two (2) or four (4) 
Strikes 

 

Test mode, Normal or Test operation 

 

The settings shown below are factory default 
for most heat pump applications, however 
the Unit wiring diagram is the ultimate guide 
for factory DIP switch default settings. 
 

 

Figure 2 - Dip switch settings 

 

The following table is available on the UPM 
board  as  well  and  it  depicts  the  switch 
position and its associated functionality. 

 

 

Selectable Alarm Mode 

 

The  UPM  controller  can  be  configured  to 
have either a constant signal or a pulse. 
 
If constant (CONT) is selected the UPM will 
provide  a  closed  contact  until  the  alarm  is 
cleared. 
 
If  pulsed  (PULSE)  is  selected  the  UPM  will 
sequence  the  alarm  contact  with  the  fault 
LED flashes. 

Freeze protection 

 

The default setting for the freeze limit trip is 
30°F; however this can be changed to 15°F 
by  cutting  the  R17  for  Compressor  1  and 
R77  for  Compressor  2  resistor  located  on 
top of the DIP switch SW1. 
 
The  UPM  controller  will  constantly  monitor 
the  refrigerant  temperature  with  the  sensor 
mounted close to the condensing water coil 
between  the  thermal  expansion  valve  and 
water coil as shown in figure 4.  

UPM DIP SWITCH CONFIGURATION 

4

LOCKOUT 4 2 

3

RESET 

2

ALARM CONT 

PULSE 

1

TEST 

YES 

NO 

Figure 3 - DIP switch table 

ON 

1

 

2

 

3

 

LOCKOUT 

RESET 

ALARM 

TEST 

Summary of Contents for FHP UPM II

Page 1: ...I O ZONE 560 583 UPM II INSTALLATION AND OPERATION MANUAL 1 ...

Page 2: ...rect part number TABLE OF CONTENTS Specifications 3 Unit Protection Module UPM 4 Power Random Start Up 5 Anti short cycle delay 5 Y Call 5 High and Low pressure protection 5 Ground 7 DIP Switch Settings 7 Selectable Alarm Mode 7 Freeze protection 7 Brownout protection 8 Condensation overflow 8 Sequence of Operation 8 UPM Sequence of Operation SOO Flow Chart 9 2 ...

Page 3: ...y contact Normally Open NO Inputs Four 9 inputs Dedicated inputs for 2 High Pressure Switches HPC 2 Low Pressure Switches LPC 2 Freeze Sensors FREEZE 10 K 77F Thermistor 1 Condensate Overflow Sensor CON 230 K 15 2 Compressor Call Y Signals Status Indication Visual LED status of power and alarms status indication Protection Surge and transient protection circuitry Weight 0 25 lbs 0 12 Kg Overall Di...

Page 4: ...sors of each refrigerant circuit this device provides time delays and protects the unit against freezing of the water and refrigerant heat exchangers as well as condensate overflow when the appropriate sensors are installed Figure 1 UPM Two Stage Alarm output is Normally Open NO dry contact If 24 VAC output is needed R must be wired to the ALR COM terminal 24VAC will be available on the ALR OUT te...

Page 5: ...ved The anti short cycle delay is 300sec delay on break during normal operation Y Call The UPM will energize the compressor s output CC in an event of a Y call from a thermostat or controller after the random start up and or the anti short cycle delays have elapsed Y input terminal must be energized with a 24 VAC signal High and Low pressure protection The UPM monitors the state of the High and Lo...

Page 6: ...or The user can select either two or four times by changing switch four 4 on the DIP switch SW1 shown on table 3 on the UPM board Low pressure protection If the LP1 or LP2 switches are open upon a Y1 or Y2 call Could be Y1 or Y2 or both the UPM will not energize the CC1 or CC2 outputs and therefore the correspondent compressor will remain off the fault LED will flash two 2 times for the LP1 and 4 ...

Page 7: ...associated functionality Selectable Alarm Mode The UPM controller can be configured to have either a constant signal or a pulse If constant CONT is selected the UPM will provide a closed contact until the alarm is cleared If pulsed PULSE is selected the UPM will sequence the alarm contact with the fault LED flashes Freeze protection The default setting for the freeze limit trip is 30 F however thi...

Page 8: ...espondent code via its status LED 6 flashes Figure 4 Freeze sensor location To exit the hard lockout water has to return to its normal level and UPM has to be reset by removing the power from the Y terminal R if set on the DIP switch the compressors will be turned on after anti short cycle expires Brownout protection The UPM controller will constantly monitor the power supply if the nominal voltag...

Page 9: ...UPM Sequence of Operation SOO Flow Chart 9 ...

Page 10: ...10 601 N W 65th Court Ft Lauderdale FL 33309 Phone 954 776 5471 Fax 954 776 5529 www fhp mfg com 6 720 220 322 REV 6 11 ...

Reviews: