14
en
FCS-LWM-1
F.01U.028.512 | A2 | 2007.03
Bosch Security Systems
DIFF TIME / DIFF ALARM calibration switch setting
The DIFFALARM features two 16-position DIFF TIME and DIFF ALARM switches that can be
adjusted separately. LWM-1 can be used for grades A1, A2, B and C.
The table below contains recommendations for special applications.
Technichal Data
Mechanics
Electrical
Application
DIFF TIME
DIFF ALARM
Response grade
Underground installation
(no road tunnels)
5
5
5
5
5
4
8
9
A1 (blue cable only)
A1 (black cable only)
A2
B
Installation on concrete ceilings
and other thermally
non-conductive material above
ground, out of direct sunlightg
5
5
5
5
6
5
4
8
9
13
A1 (blue cable only)
A1 (black cable only)
A2
B
C
Installation on insulated steel roof
or metal container, out of direct
sunlight
5
5
5
5
6
5
4
8
9
13
A1 (blue cable only)
A1 (black cable only)
A2
B
C
Installation on non-insulated steel
roof or in direct sunlight
5
6
9
13
B
C
Road tunnel
5
5
5
5
6
5
4
8
9
13
A1 (blue cable only)
A1 (black cable only)
A2
B
C
i
NOTICE!
If a false alarm is triggered by the DIFF ALARM, proceed as follows:
–
Shorten the sensor cable for each control unit
–
Reduce the response grade, e.g. from A1 to A2
Housing material
ABS
Overall dimensions
200 mm x 120 mm x 80 mm (W x H x D)
Weight
approx. 550 g
Displays
Green LED: in operation, continuously lit
Red LED: ALARM DIFF, continuously lit
Red LED: ALARM MAX, continuously lit
Yellow LED: malfunction, flashing light
Test keys
2 x for simulating alarm, malfunction and LED test
Protection type
IP 65
Color
Gray, similar to RAL 7035
Temperature range
- 20 °C bis + 50 °C
Voltage
10 - 30 V DC
Standby current consumption
Max. 25 mA (with 24 V)
Current consumption with DIFFALARM/MAX ALARM
Max. 25 mA (with 24 V)
Current consumption with malfunction
Max. 15 mA (with 24 V)
Switch-on current
< 100 mA (with 24 V)