Automatic detector
Technical Specifications | en
9
Bosch Sicherheitssysteme GmbH
Installation manual
2019.11 | 5 | F.01U.002.682
Indicator output
Open collector connects 0
V over 1.5
kΩ
through, max. 15
mA
Minimum installation height
Out of arm's reach
Minimum installation height recommended by
BOSCH: 2.70
m
Maximum installation height
16
m (heed local guidelines)
Minimum distance to lamps
50
cm
Permissible operating temperature
FAP‑O
520(-P): -20
°C to +65
°C
FAP‑OC
520(-P): -10 °C to +50
°C
Permissible rel. humidity
<95
% (non-condensing)
Permissible air speed
20
m/s
Protection class as per IEC
60529
FAP‑O 520(-P): IP
53
FAP‑OC 520(-P): IP
33
Weight (without/with packaging)
FAP‑O 520(-P): 170
g/360
g
FAP‑OC 520(-P): 180
g/370
g
Summary of Contents for FAP-520