IP30 IK04 (EN 60529, EN 62262)

0 - 95% Relative Humidity
(0 - 85% UL Installations)  

-40°C to +49°C

(-40°F to +120°F )

UL Listed

installations,

the temperature

range  is  0°C  to  +49°C          

(+32°F to +120°F)

För svensk installationsanvisning se www.boschsecurity.se.

1 Installation Considerations

Never install the detector in an environment that causes an alarm 

condition in one technology. Good installations start with the LED off 

when there is no target motion. It should never be left to operate with the 

tri-color LED in a constant or intermittent green, yellow, or red condition.

NOTICE!

Microwave energy will pass through glass and most common 

non-metallic construction walls.

Eliminate interference from nearby outside sources.

Point the unit away from outside traffic (roads/alleys).

2 Mounting

Select a location likely to intercept an intruder moving beneath and across 

the coverage pattern. Recommended mounting height range is 8 to 18 feet 

(2.4 to 5.5 m).
The surface should be solid and vibration-free. (i.e. Drop tiles should be 

secured if the area above the tiles is used as an air return for HVAC sys-

tems).
1. Remove the base from the enclosure by pressing the two enclosure

release tabs inward while lifting the enclosure away from the base.

Refer to 

Figure 2.1

.

nclos re  elease  a s

Base

Enclosure

Cover

The Cover remains

attached to the

Enclosure

Anti-vandal locking screw holes

Figure 2.1: Opening cover

Specifications
Dimensions 

(HxDia)

3.5 in. x 5.25 in. (8.9 cm x 13.3 cm)

Input 

Power

6.0 to 15.0 VDC; 8 mA standby, 60 mA in alarm with LEDs enabled. Use only an Approved 
Limited Power Source.

Standby 

Power

There is no internal standby battery. Standby power must be provided by an Approved 
Limited Power Source. Eight mAh required for each hour of standby time needed. For UL 
Listed Requirements, 32 mAh standby current is required.

Alarm Relay Silent-operating Form “C” relay. Contacts rated <100 mA, 25 VDC, 2.5W <20 Ohm closed 

maximum for DC resistive loads. 

Tamper

Contacts rated at 28 VDC, 125 mA maximum, <1 Ohm. To be connected to a SELV (Safety 
Extra-Low Voltage) circuit only. Connect tamper circuit to a 24-hour protection circuit.

Compliance This device complies with Part 15 of the FCC Rules. Operation is subject to the following 

two conditions:

(1) this device may not cause harmful interference, and

(2) this device must accept any interference received, including interference that may

cause undesirable operation.

NOTICE!

Slightly rock the enclosure side-to-side during removal to overcome the 

friction caused by the base-to-enclosure terminal pins.

SELV

Connect all wiring to a safety extra-low voltage (SELV) circuit only.

Ligue todas as cablagens apenas a um circuito de segurança de tensão extra baixa.

Conecte el cableado únicamente a un circuito de seguridad para voltajes muy bajos.
Alle Drähte sind ohne Ausnahme an Niederspannung anzuschließen.
Sluit alle bedrading uitsluitend aan op een circuit met een extra lage veiligheidsspanning.

Prenez soin de connecter tous les câbles à un circuit à très basse tension de sécurité (TBTS).

Collegare tutti i cavi esclusivamente a un circuito di sicurezza a bassissima tensione.

Changes or modifications not expressly approved 

by Bosch Security Systems, Inc. can void the user’s 

authority to operate the equipment.
UL

Perform Walk Test at least once a year.

Use only a Listed limited-power source.

The Listed control unit or a Listed burglary power 

supply must provide 4 hours (32 mAh) of standby 

power.

Install the unit in accordance with National 

Electrical Code NFPA 70.

Adjust the microwave range control, if necessary, to 

achieve maximum range.

2. Open the cover by turning counterclockwise. One side of the cover will

remain attached to the base of the detector. Do not attempt to entirely

remove the cover. Refer to 

Figue 2.1

.

3. Route wiring as necessary to the rear of the base and through the

center hole. Refer to 

Figure 2.2

.

Summary of Contents for DS9360

Page 1: ...tecodes 8 Fonctions de surveillance Les fonctionnalités de surveillance fonctionnent comme suit IRP hyperfréquences l intégralité du circuit de ces sous systèmes est vérifiée toutes les 6 heures environ En cas de défaillance du sous système IRP ou hyperfréquences la LED rouge clignote 4 fois par cycle et l appareil doit être remplacé Par défaut le détecteur passe en mode de protection IRP en cas d...

Page 2: ...rrent is required Alarm Relay Silent operating Form C relay Contacts rated 100 mA 25 VDC 2 5W 20 Ohm closed maximum for DC resistive loads Tamper Contacts rated at 28 VDC 125 mA maximum 1 Ohm To be connected to a SELV Safety Extra Low Voltage circuit only Connect tamper circuit to a 24 hour protection circuit Compliance This device complies with Part 15 of the FCC Rules Operation is subject to the...

Page 3: ...p the new module into place 4 Replace the enclosure onto the base 5 Close cover and turn clockwise to secure NOTICE Avoid fingerprints on the mirrored surfaces Should the mirrored sur faces become soiled or otherwise marked they can be cleaned using a soft clean cloth and any commonly available mild window cleaner 3 Wiring CAUTION Only apply power after all connections have been made and inspected...

Page 4: ...tivity mode 7 3 Microwave Adjustment NOTICE It is important to wait 1 minute after removing replacing the cover so the microwave portion of the detector can settle and to wait at least 5 seconds between the following walk testing procedures 1 The tri color LED should be off before walk testing 2 Walk test across the pattern at the intended coverage s farthest end Start walking from outside the int...

Page 5: ...Security Systems B V web site at http www boschsecurity com datecodes 8 Supervision Features The supervision features function as follows PIR Microwave The complete circuit operation of these subsystems is checked approximately every 6 hours If the PIR or microwave subsystem fails the red LED will flash 4 times per cycle and the unit should be replaced Default The detector will default to PIR tech...

Page 6: ...ntacts de valeurs nominales 100 mA 25 Vdc 2 5 watts 20 ohms fermés maximum pour charges résistives en courant continu Autosurveil lance Contacts de valeurs nominales 28 Vdc 125 mA maximum 1 ohm Doit être connecté au circuit très basse tension de sécurité TBTS uniquement Connectez le circuit d autosurveillance au circuit de protection 24 heures Conformité Cet appareil est conforme aux exigences imp...

Page 7: ... base 5 Fermez le couvercle et verrouillez le en le tournant dans le sens des aiguilles d une montre ATTENTION Évitez les traces de doigts sur les surfaces à miroir Si les surfaces à miroir sont sales ou portent des marques elles peuvent être nettoyées à l aide d un chiffon propre et doux et d un nettoyant de fenêtre doux quelconque 3 Câblage ATTENTION Mettez le dispositif sous tension uniquement ...

Page 8: ... conditions environnementales normales Le détecteur est réglé par défaut sur le mode Sensibilité élevée 7 3 Ajustement d hyperfréquences ATTENTION Il est important d attendre 1 minute après le retrait ou le remplacement du couvercle de façon à ce que la partie hyperfréquences du détecteur puisse s ajuster et d attendre au moins 5 secondes entre les procédures de test de détection suivantes 1 La LE...

Reviews: