Notification Appliance Circuit Module
Notices | en
3
Bosch Security Systems, Inc.
Installation manual
2020.05 | 04 | 4998122260
1
Notices
These instructions cover the installation of the D192G Notification Appliance Circuit Module in
a fire system supervised by a fire alarm control panel (FACP) or a combination Burglary/Fire
control panel.
Install, test and maintain the module according to these instructions, NFPA codes, local codes,
and the authority having jurisdiction (AHJ). Failure to follow these instructions can result in
failure of a detector to initiate an alarm event. Bosch Security Systems, Inc. is not responsible
for improperly installed, tested or maintained devices.
Before installing the module, become familiar with the Installation and Operation Guide for
the control panel you are using.
The module uses only polarized (DC) signaling devices. Not all signaling devices are polarized.
The signaling devices used with the module must:
–
be polarized (DC) signaling devices.
–
match the voltage rating of the alarm power supply.
–
not exceed the current rating of the alarm power supply.
–
not exceed 3 A per module.
–
total no more than 12 D192G modules per system.
!
Warning!
Follow these instructions to avoid personal injury and damage to equipment.
NFPA 72 requires that you perform a complete system wide functional test following any
modifications, repair, upgrades or adjustments made to the system’s components, hardware,
wiring, programming and software/firmware.