D1256/D1257
Installation
© 2004 Bosch Security Systems
130 Perinton Parkway, Fairport, NY 14450-9199 USA
Customer Service: (800) 289-0096; Technical Support: (888) 886-6189
74-06925-000-H
Installation Instructions
12/04
D1256/D1257
Page 16 of 16
Further customization can be required if the D1256 is connected to a D7212B1, D9112B1, or D9124 (using
the D9112LTB) is located in an unsecured area, and/or if D1255 Command Centers are installed in the same
system. The factory loaded program for the D9124 makes these functions available without requiring a
passcode entry.
For example, the D1256 is connected to a D7212B1, D9112B1, or D9124 (using the D9112LTB) located in a
secure area, but the D1255 Command Centers are also installed, restricting command center functions by
requiring a passcode in Cmd Center Function is advisable.
Note:
For D7212B1, D9112B1, or D9124 (using the D9112LTB) Control Panels, it is important to program each of the
command center functions with an E (Enabled) and not P (Passcode Required). If any of the command center
functions are programmed with a P (Passcode Required)
,
then that custom function must also be programmed to
execute that menu item from the command center. This custom function must include the appropriate passcode to
let the programmed function work properly. For example, if View Event Memory were to be passcode protected
and the chosen passcode was 125600, the macro string would be
[A][4][0][1][2][5][6][0][0][E]
. Consideration
should be given to passcode protecting the command center function in combined burglary/fire applications.
Function numbers for standard User Interface command center functions can be programmed in the Menu
Function List for D1256 and D1255 addresses. Remember to enable functions only as appropriate for the
command center at the address. As the D1256 does not have numeric keys, it can not be used to access functions
requiring a passcode.
Note:
For D7212, D7212G, D7412, D7412G, D9112, D9412, D9412G and D9124 (using the D9112LTB-EX or
D9412GLTB) Control Panels, embedding passcodes inside Custom Functions is not allowed. Therefore, any
command used in a Custom Function, should not be passcode protected.
Please make sure that CF
128
to 131 and any other functions that you are using in the menu are programmed
E (Enabled) not P (Passcode Required).