24 / 40
ctrlX CORE
Electric installation
Bosch Rexroth AG
R911405645, Edition 03
Use only power supply units that can bridge a half-wave failure (10 ms).
10.5.2 Power connector XD10
The control is supplied via the XD10 plug.
Connect the power connector with cables with a conductor cross-section of AWG 16
(1.5
mm
2
).
Use only copper wires to connect the connection terminals.
Use only cables approved for temperatures of at least 60°C.
Only the power connector is permitted to connect the 24 V supply voltage for the control (see
Chapter 5.1 “Power connectors, 24 V” on page 11
).
1
2
Fig. 12: Power connector XD10
Table 13: Pin assignment of the power connector XD10
Plug contact
Signal
Function
1
24 V
+24 V DC supply voltage (U
L
)
2
0 V
GND (U
L
) (ground supply voltage)
Mounting notes:
•
For the XD10 plus, one-wire cables and stranded cables can be used with or without wire end fer-
rule.
•
The cable cross-section allowed is between 0.25 and 1.5 mm (AWG 24 to 16).
•
Die stripping length is 8 mm.
•
If stranded cables are used without wire end ferrules, press the pushbutton of the spring clip when
introducing the slightly twisted stranded cable.
•
To remove the cables, press the pushbutton of the spring clip.
10.5.3 24 V voltage supply
The voltage supply (SELV) for the device has to be equipped with a UL-approved overcurrent
protection acc. to UL 61010-1, table 18.
For the voltage supply, use a power supply unit as described in the following chapter: