6 |
Control Air M/M+ Water to Water Applications
Installation & Operation Manual
02.2019 | BTC 469503103 A
Data subject to change
3 Speci
fi
cations
Description
Value
Power
24 Vac (+/-15%), 5 VA, 50-60 Hz, Class 2
Backlit LCD display
4.3" resistive touchscreen color LCD discplay with backlighting WQVGA 480x272 px
Cable
6 ft. (1.8 m) cable to connect to controller's Local Access port.
Communication
Rnet: 2-wire EIA-485 port for connection to the Rnet sensor network (115 kbps)
Memory
—
16 MB Flash memory to store screen file.
—
1.5 MB RAM to store variable data and LCD data.
—
4 KB Serial EEPROM to store non-volatile configuration data.
Operating Range
-4° to 140°F (-20°C to 60°C), 10%-90% RH noncondensing
Overall dimensions
—
Width: 5-7/16 in. (138mm)
—
Height: 4-1/16 in. (116mm)
—
Depth: 1-3/8 in. (30mm)
Weight
0.54 lbs (0.24 kg)
Listed by
UL-916 (PAZX), CE, FCC Part 15-Subpart B-Class A
Temperature Sensor
—
Range @ 95% RH: -4°F to 140°F (-20°C to 60°C)
—
Range @ 20% RH: -4°F to 194°F (-20°C to 90°C)
—
Accuracy @ 25°C: ±0.4°C
—
Accuracy over 20°C to 30°C: ±0.5°C
—
Accuracy over 10°C to 45°C: ±1.0°C
—
Accuracy over full range: ±2.5°C
—
Resolution: 0.01°C
Humidity Sensor
—
Range: 0 to 100% RH
—
Accuracy over 20 to 80% RH: ±3.0% RH
—
Accuracy over full range: ±5.0% RH
—
Resolution: 0.05 RH
Table 1
Speci