 Installation & Operation Manual 

                                                                                     

Control Air M/M+ Water to Water Applications

 

| 11

   

BTC 469503103 A | 02.2019

            

 Data subject to change

7     How to Navigate Screens in Control Air M/M+

7.1     Login

The following displays if the screen you selected requires a password. 
Enter your password, then touch 

Done.

Figure 10

Each screen is programmed with one of the following password levels:

A screen having this 
password level…

Can be accessed by…

User

A user logged in with the User, Admin, or 

Factory password

Admin

A user logged in with the Admin or Factory 

password

Factory

A user logged in with the Factory password

No password

Anyone

Table 4

 

 

  The default password for a new Control Air M/M+ is 0000.

 

  You can change passwords on the Control Air M/M+ by going to 

Touchscreen Setup > Passwords screen.

You log out on the Setup screen.

7.2     Alarms

The Alarm screen allows the user to view up to 100 events starting with 
the most recent. It also allows user to see which points have gone into 
alarm and retuned to normal as well as the ones that have been manually 
cleared. 

Figure 11

7.3     Trends

Figure 12

This screen can be accessed from the Help Screen on the Service page 
(Home -> Service -> Help -> Trends). It allows the end user to view trends 
for points that have trending enabled.

Figure 13

Summary of Contents for Control Air M

Page 1: ...Control Air M and M For Commercial Water to Water DDC Applications Installation Operation Manual BTC 469503103 A 2019 02 US ...

Page 2: ...2 Control Air M M Water to Water Applications Installation Operation Manual 02 2019 BTC 469503103 A Data subject to change ...

Page 3: ...ecting Control Air M M to a Controller 9 7 How to Navigate Screens in Control Air M M 11 7 1 Login 11 7 2 Alarms 11 7 3 Trends 11 8 To Update the Control Air M M s Firmware 12 8 1 Prerequisite 12 8 2 To Update the Firmware 12 8 3 Resetting the Control Air M M 12 8 4 Compliance 13 9 The Control Air M and M Screens 14 9 1 Units Status Screen Home Page 14 9 2 Settings Screen 14 9 2 1 Unit Settings Sc...

Page 4: ...n where there is no risk to people or property 1 2 Safety Warnings WARNING ELECTRIC SHOCK HAZARD Installation and servicing of this equipment can be hazardous due to the electrical components Only trained and qualified personnel should install repair or service the equipment WARNING ELECTRIC SHOCK HAZARD Before performing service or maintenance operations on the system turn off main power to the u...

Page 5: ...touchscreen device with a 4 3 color LCD display that you connect to a Control Air 5600 to view or change its property values schedule units view trends and alarms and more The unit connects to the controller via the onboard serial port The module can be purchased by the following part numbers Control Air M 8733951042 Control Air M 8733951043 ConnectingCable VirtualControlAirM M only 8733908163 The...

Page 6: ...1 5 MB RAM to store variable data and LCD data 4 KB Serial EEPROM to store non volatile configuration data Operating Range 4 to 140 F 20 C to 60 C 10 90 RH noncondensing Overall dimensions Width 5 7 16 in 138mm Height 4 1 16 in 116mm Depth 1 3 8 in 30mm Weight 0 54 lbs 0 24 kg Listed by UL 916 PAZX CE FCC Part 15 Subpart B Class A Temperature Sensor Range 95 RH 4 F to 140 F 20 C to 60 C Range 20 R...

Page 7: ...Data subject to change 4 Physical Dimensions Figure 3 Side View Right Back View with Mounting Plate Side View Left Back View without Mounting Plate Mounting Plate 1 242 5 440 5 440 4 550 4 550 3 938 4 799 Control Air M M Module Termination Details Figure 4 Back View with Mounting Plate Mounting Plate ...

Page 8: ...VC or equivalent Color Code Black white green red Shielding If shielded Aluminum Mylar shield 100 coverage with TC drain wire Table 3 6 Connection 6 1 Communicate Using a Tablet Through Virtual Control Air M and M In lieu of using the module to interface with the controller a connection may be established at the local access port of the controller to perform testandbalanceoperationsortomakechanges...

Page 9: ...nect the other end of the Rnet wiring to the controller s Rnet port or to a zone sensor Insert the shield wire with the ground wire into the controller s GND terminal Use the same polarity throughout the Rnet or MS TP 11 Connect power wiring to a 24 Vac power supply 12 Turn on the controller s power 6 3 Additional Information on Connecting Control Air M M to a Controller Connect the Control Air M ...

Page 10: ...ctor Establishing Communication Plug the USB L cable to the USB Bosch part number 8733 927 403 to USB micro adapter field supplied and then to the Android tablet and controller before launching Virtual Control Air M M Equipment Touch OEM app The DDC controller must be connected to a 24 VAC source and powered on Figure 9 8733 927 403 Not provided by Bosch ...

Page 11: ...actory password Factory A user logged in with the Factory password No password Anyone Table 4 The default password for a new Control Air M M is 0000 You can change passwords on the Control Air M M by going to Touchscreen Setup Passwords screen You log out on the Setup screen 7 2 Alarms The Alarm screen allows the user to view up to 100 events starting with the most recent It also allows user to se...

Page 12: ...ve 8 3 Resetting the Control Air M M You can create a reset dat file and put it on a USB flash drive to reset some of the Control Air M M s functionality Prerequisite The USB flash drive must be formatted as FAT FAT16 or FAT32 To verify right click the flash drive in Windows Explorer then select Properties File system should show FATxx If File system shows NTFS or anything else you must reformat the d...

Page 13: ...likely to cause harmful interference in which case the user will be required to correct the interference at his own expense NOTICE HARMFUL INTERFERENCE HAZARD Changes or modifications not expressly approved by the responsible party for compliance could void the user s authority to operate the equipment CE Compliance NOTICE HARMFUL INTERFERENCE HAZARD This is a Class A product In a domestic environ...

Page 14: ...nce all operational parameters are configured these settings may be saved and archived to flash memory by selecting the Save Settings check box Figure 16 Occupancy Command Under the Unit Settings screen this parameter is used to select the control source that will provide the occupancy command to the unit The options for this variable are the following Digital Input Local Schedule BAS Command Manual...

Page 15: ...s selected when unit has 2 compressors and each compressor will operate as an independent stage 1 Compressor 2 Stages This value is selected when unit has 1 compressor that has two independent stages This is the default setting from the factory 1 Compressor 1 Stage This value is selected when unit has 1 compressor with only 1 stage of operation Mode Selection Method This setting is similar to a th...

Page 16: ... 2 Communication This screen lets you edit the information below for the controller Figure 21 Touch a field to tap in new information BACnet Device Instance number Auto Generate Device ID Enter No or Yes You can edit the following fields that pertain to the controller s MS TP network Max Masters Set this to the highest MAC address up to 127 on the MS TP network If you later add a device with a highe...

Page 17: ...will then send time broadcasts only to controllers on its ARCnet or MS TP network 2 Global Broadcast If it doesn t already exist a global address with network number set to 65535 and MAC address length set to zero is added to the controller s Time Synchronization Recipients list found on the driver s Device page in WebCTRL The controller will then send time broadcasts to all its connected networks...

Page 18: ... sound when you touch a field or button Touch Key Click On to turn on the sound Alarm Sound Off On Touch Alarm Sound Off to turn off the alarm notification sound or touch Alarm Sound On to turn on the sound An alarm will generate a sound only if it is set up by Bosch Reload Firmware Erases the current firmware so that you can load new firmware through the USB port See To update the Control Air M M s firmw...

Page 19: ... pump was started after its corresponding reset Pump Start Counter Last hr This value indicates how many times in the last hour the pump was started Figure 28 9 2 5 Temperature The Temperature Screen can be accessed from the home page through the Settings menu This screen allows the user to view the following temperatures and temperature setpoints Entering water temperature Leaving water temperatu...

Page 20: ...default To change to weekly view click drop down option and change accordingly Week View Figure 34 Which days of the week shown have schedules indicated by green bars If you see Schedule editing disabled at the bottom of the screen instead of Add Schedule scheduling is being done through another application and is disabled for the Control Air M Touch a day to see the schedule s for that day In the...

Page 21: ... every Monday through Friday 8 00 am to 5 00 pm Continuous Continuously between 2 specified dates times For example a non stop schedule that starts June 1st at 12 00 am and ends August 31st at 11 50 pm Table 9 ON Schedule only Select one normal for this example of the following Normal for a typical occupied period Override for a occupied period that is to override an OFF schedule Touch Next to defin...

Page 22: ...rameter displays how many compressors compressor stages are being called Compressor rotation frequency This parameter gives the user the option to set the frequency at which the compressors are switched from lead to lag or vice versa Based on this selection the user can set the next parameter value accordingly Figure 40 Figure 41 9 3 Service Screen The Service menu allows the qualified technician t...

Page 23: ... for the cooling and heating operation respectively The runtime hours and counters for the compressors are displayed and can be reset by navigating selecting and changing the particular value Figure 47 Figure 48 9 3 2 UPM Status Screen The UPM Status screen can be accessed from the home Screen via the Service Menu Once an alarm is received via pulse feedback from the UPM board it is displayed in t...

Page 24: ...he controller to which they are connected Other information on this screen include the controller part number and unit serial number This information will be useful whenever technical support is contacted or may be required to download the correct manuals or integration point list files from our website The technical support phone numbers can also be found in this screen In addition troubleshooting...

Page 25: ...Installation Operation Manual Control Air M M Water to Water Applications 25 BTC 469503103 A 02 2019 Data subject to change ...

Page 26: ...26 Control Air M M Water to Water Applications Installation Operation Manual 02 2019 BTC 469503103 A Data subject to change ...

Page 27: ...Installation Operation Manual Control Air M M Water to Water Applications 27 BTC 469503103 A 02 2019 Data subject to change ...

Page 28: ...United States Bosch Thermotechnology Corp 65 Grove Street Watertown MA 02472 Tel 866 642 3198 Fax 603 965 7581 www boschheatingandcooling com BTC 469503103 A 02 2019 ...