11.0 Network Communications
The D6600 Central Station Communications
Receiver/Gateway NetCom system supports data
network communications. NetCom allows the D6600
Receiver to connect to Ethernet networks, and process
messages both to and from most networks in user
datagram protocol (UDP) or internet protocol (IP). Use
a COM4 or a COM1 connection from the D6600
Receiver to connect to the network adapter. Central
station automation software, through a local-area
network (LAN) or wide-area network (WAN), receive
reports from alarm control panels from the PSTN, or
other data networks. The automation software also
monitors the control panel status and connection over
the network. Update or upgrade the D6600 through the
network connection. Use the D6200 software to remote
program the D6600. Refer to the following documents
about network communications and their installation
requirements.
•
NetCom System Guide (P/N: 4998122712)
•
D9133TTL-E Installation Guide (P/N: 4998122717)
•
C900TTL-E Installation Guide (P/N: 4998122718)
•
DX4020 Installation Guide (P/N: 49522)
•
D6680 Network Adapter Installation Guide
(P/N: 4998138732)
•
DeviceInstaller Operation and Installation Guide
(P/N: 4998138688)
Figure 14: D6600 NetCom System Connection
Diagram - C900TTL-E and Any Control
Panel
PANEL
TELCO
1
2
3
4
5
5
6
7
8
9
10
11
12
13
1
Any manufacturer’s control panel
2 C900TTL-E
Dialer
Capture
Module
3
Host PC running D6200 Programming
Administrative Software
4 Ethernet
hub
5
D6680 Network Adapter
6
D6600 Central Station Receiver (CSR)
7
Connection - Control panel telco jack to
C900TTL-E jack
8
Connection - C900TTL-E Ethernet jack to
Ethernet hub
9
Connection - Host PC network interface card
(NIC) to Ethernet hub
10 Connection – Ethernet hub to D6680
11 Connection – Ethernet hub to second D6680
12 Connection – D6680 to D6600 COM4 port
13 Connection – Second D6680 to D6600
COM 1 port (optional)