CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
Product Features
Displayed code
Explanation
Displayed value
Meaning
Additional Notes
T1
Room temperature
-1F,-1E,-1d,-1c,
-1b,-1A
-19—99
A0,A1,…A9
b0,b1,…b9
c0,c1,…c9
d0,d1,…d9
E0,E1,…E9
F0,F1,…F9
-25,-24,-23,-22,
-21,-20
-19—99
100,101,…109
110,111,…119
120,121,…129
130,131,…139
140,141,…149
150,151,…159
1. All displayed temperatures use
actual values.
2. All temperatures are displayed in
°C regardless of remote used.
3. T1, T2, T3, T4, and T2B display
ranges from -25 to 70 °C. TP
display ranges from -20 to 130 °C.
4. The frequency display ranges from
0 to 159HZ.
5. If the actual values exceed or fall
short of the defined range, the
values closest to the maximum and
minimum values will be displayed.
T2
Indoor coil temperature
T3
Outdoor coil tempera-
ture
T4
Ambient temperature
TB
Outlet temperature of
indoor coil
TP
Discharge temperature
TH
Suction temperature
FT
Targeted frequency
FR
Actual frequency
IF
Indoor fan speed
0
1,2,3,4
14-FF
OFF
Low speed, Medium
speed, High speed,
Turbo.
Actual fan speed is
equal to the display
value converted to
decimal value and
multiplied by 10. This
is measured in RPM.
N/A
Used for some large capacity motors.
Used for some small capacity motors.
The display value is 14-FF (hexadec-
imal). The corresponding fan speed
ranges from 200 to 2550RPM.
OF
Outdoor fan speed
LA
EXV opening angle
0-FF
Actual EXV opening
value is equal to the
display value converted
to decimal value and
then multiplied by 2.
-
CT
Compressor continuous
running time
0-FF
0-255 minutes
If the actual value exceeds or falls
short of the defined
range, the value closest to the maxi-
mum and minimum will be displayed.
ST
Causes of compressor
stop
0-99
For a detailed explana-
tion, contact technical
support.
-