6 720 862 438 (2016/04)
RDCI Series – All DC Inverter Outdoor Units
6 | FORCE COOLING AND QUERY
6. FORCE COOLING AND QUERY
■
Force Cooling
Once the Force Cooling button has been pressed (see diagram), all the
indoor units will be forced into cooling mode and the fan speeds will be
running on maximum.
Fig. 6-1
■
SW2 Display Codes
Table 6-1
No.
Normal display
Display content
Note
1
0. --
Outdoor unit address
0,1,2,3
2
1. --
Individual Outdoor unit capacity
8,10,12,14,16
3
2. --
Modular outdoor unit qty.
Available for main unit
4
3. --
Operation mode
0,2,3,4,5,6
5
4. --
Total capacity of outdoor units
Capacity requirement
6
5. --
Cooling capacity
(Auxiliary unit only) display capacity for main mode
7
6. --
Heating capacity
(Auxiliary unit only) display capacity for main mode
8
7. --
T4 ambient temp. revision of cooling capacity
9
8. --
T4 ambient temp. revision of heating capacity
10
9. --
The outdoor unit actual operating capacity
Capacity requirement
11
10. --
Speed of fan A
0, 1,······,14,15
12
11. --
Speed of fan B
0, 1,······,14,15
13
12. --
T2 average temp.
Actual value
14
13. --
T2B average temp.
Actual value
15
14. --
T3 pipe temp. (Left pipe temp.)
Actual value
16
15. --
T5 pipe temp. (Right pipe temp.)
Actual value
17
16. --
T4 ambient temp.
Actual value
18
17. --
Discharge temp. of inverter compressor A
Actual value
19
18. --
Discharge temp. of inverter compressor B
Actual value
20
19. --
Modual temp.
Actual value
21
20. --
Discharge pressure corresponding to the saturation temperature
Actual value + 30
22
21. --
The minimum overheating temp. of discharge
Actual value
23
22. --
Current of inverter compressor A
Actual value
24
23. --
Current of inverter compressor B
Actual value
25
24. --
State of the evaporator or condenser
0,1,2,3
26
25. --
Opening angle of EXV A
Actual value ÷ 8
27
26. --
Opening angle of EXV B
Actual value ÷ 8
28
27. --
High pressure
Actual value × 10
29
28. --
Qty. of indoor units
That can communicate with indoor units
30
29. --
Qty. of cooling indoor units
Actual value
31
30. --
Qty. of heating indoor units
Actual value
32
31. --
Reserve
33
32. --
Night noise control mode
0,1,2,3
34
33. --
Static pressure mode
0,1,2,3
35
34. --
DC voltage A
Actual value÷10
36
35. --
DC voltage B
Actual value÷10
37
36. --
Reserve
38
37. --
Reserve
Display code 8.8.8
39
38. --
Remove fault number of times
40
39. --
Check end
MAIN BOARD
(OUTDOOR UNIT)
Query button
Forced cooling button
CHECK
COOL