RDCI Series – All DC Inverter Outdoor Units
6 720 862 438 (2016/04)
MALFUNCTION | 5
5. MALFUNCTION
Table 5-1
No.
Error code
Error or protection type
Note
1
E0
Outdoor unit communication error
Only displays on auxiliary unit
2
E1
Phase error
3
E2
Communication error with indoor unit
Should there be no communication after 20 minutes from
when the unit is first powered up or no communication for
longer than 2 minutes after the 20 minutes initial power up
4
E4
Outdoor temp. sensor error
5
E5
Voltage protection
6
E7
Discharge sensor error
Once the unit has run for 10 minutes, the unit will allow a
discharge temperature of less than 15 degrees at a pressure
of more than 3.5MPa for 2 minutes. After 2 minutes the
unit will fault and will have to be powered off/ on to reset the
fault.
7
E8
Outdoor unit address error
8
xE9
S11 setting does not match the capacity
9
xH0
Communication error between DSP and main chip
X represents a system, 1 is
A system
, 2 is B system
10
H1
Communication error between 0537 and main chip
X represents a system, 1 is
A system
, 2 is B system
11
H2
Qty. of outdoor units decreases error
Only displayed on main unit
12
H3
Qty. of outdoor units increases error
Only displayed on main unit
13
xH4
P6 protection has been activated 3 times in 60 minutes
Must restart electrical power supply to unit to clear the fault
14
H5
P2 protection has been activated 3 times in 60 minutes.
Must restart electrical power supply to unit to clear the fault
15
H6
P4 protection has been activated 3 times in 100 minutes.
Must restart electrical power supply to unit to clear the fault
16
H7
Qty. of indoor units not recognised
Indoor units communication lost for more than 3
munites
;
Fault will no clear until the quantity of units are recovered
17
H8
High pressure sensor error
Air discharging pressure Pc
≤ 0.3MPa
18
H9
P9 protection has been activated 3 times in 60 minutes
Must restart electrical power supply to unit to clear the fault
19
C7
PL protection has been activated 3 times in 100 minutes.
Must restart electrical power supply to unit to clear the fault
20
xHd
Auxiliary unit error (X=1,2,3, e.g, 1Hd stands for auxiliary unit1 error)
X represents an auxiliary unit
21
P0
Inverter compressor maximum temp. protection
22
P1
High pressure protection
23
P2
Low pressure protection
Should ‘P2’ fault occur more than 3 times in 60 minutes, the
unit will then display ‘H5’ fault
24
xP3
Compressor current protection
X represents a system, 1 is
A system
, 2 is B system
25
P4
Discharge temp. protection
Should ‘P6’ fault occur more than 3 times in 100 minutes,
the unit will then display ‘H6’ fault
26
P5
High condenser temp. protection
27
x (P6)
Inverter module protection
X represents a system, 1 is
A system
, 2 is B system. Should
‘P6’ fault occur more than 3 times in 60 minutes, then the
unit will display a ‘H4’ fault. If ‘H4’ fault is displayed for more
than 10 minutes, then ‘xP6’ fault will be displayed
28
P7
Main inverter current protection
29
P8
Auxiliary inverter current protection
30
P9
DC fan protection
Should ‘P9’ fault occur more than 3 times in 60 minutes, the
unit will then display ‘H9’ fault
31
PL
Main inverter module temp. protection
32
xL0
DC compressor module error
X represents a system, 1 is
A system
, 2 is
B system
33
xL1
DC bus low pressure protection
X represents a system, 1 is
A system
, 2 is
B system
34
xL2
DC bus high pressure protection
X represents a system, 1 is
A system
, 2 is
B system
35
xL3
Reserve
X represents a system, 1 is
A system
, 2 is
B system
36
xL4
MCE error/synchronization/closed loop
X represents a system, 1 is
A system
, 2 is
B system
37
xL5
Zero speed protection
X represents a system, 1 is
A system
, 2 is
B system
38
xL6
Reserve
X represents a system, 1 is
A system
, 2 is
B system
39
xL7
Phase error protection
X represents a system, 1 is
A system
, 2 is
B system
40
xL8
Protection should the speed change be greater than 15 Hz before and
after
X represents a system, 1 is
A system
, 2 is
B system
41
xL9
Protection should the required speed fluctuate by more than 15Hz
X represents a system, 1 is
A system
, 2 is
B system