RDCI Series – All DC Inverter Outdoor Units 

6 720 862 438 (2016/04)

MALFUNCTION  |  5

5.  MALFUNCTION

Table 5-1

No.

Error code

Error or protection type

Note

1

E0

Outdoor unit communication error

Only displays on auxiliary unit

2

E1

Phase error

3

E2

Communication error with indoor unit

Should there be no communication after 20 minutes from 
when the unit is first powered up or no communication for 
longer than 2 minutes after the 20 minutes initial power up

4

E4

Outdoor temp. sensor error

5

E5

Voltage protection

6

E7

Discharge sensor error

Once the unit has run for 10 minutes, the unit will allow a 
discharge temperature of less than 15 degrees at a pressure 
of more than 3.5MPa for 2 minutes.  After 2 minutes the 
unit will fault and will have to be powered off/ on to reset the 
fault.

7

E8

Outdoor unit address error

8

xE9

S11 setting does not match the capacity

9

xH0

Communication error between DSP and main chip

X represents a system, 1 is 

A system

, 2 is B system

10

H1

Communication error between 0537 and main chip

X represents a system, 1 is 

A system

, 2 is B system

11

H2

Qty. of outdoor units decreases error

Only displayed on main unit

12

H3

Qty. of outdoor units increases error

Only displayed on main unit

13

xH4

P6 protection has been activated 3 times in 60 minutes

Must restart electrical power supply to unit to clear the fault

14

H5

P2 protection has been activated 3 times in 60 minutes.

Must restart electrical power supply to unit to clear the fault

15

H6

P4 protection has been activated 3 times in 100 minutes.

Must restart electrical power supply to unit to clear the fault

16

H7

Qty. of indoor units not recognised

Indoor units communication lost for more than 3

 munites

Fault will no clear until the quantity of units are recovered

17

H8

High pressure sensor error

Air discharging pressure Pc 

≤ 0.3MPa

18

H9

P9 protection has been activated 3 times in 60 minutes

Must restart electrical power supply to unit to clear the fault

19

C7

PL protection has been activated 3 times in 100 minutes.

Must restart electrical power supply to unit to clear the fault

20

xHd

Auxiliary unit error (X=1,2,3, e.g, 1Hd stands for auxiliary unit1 error) 

X represents an auxiliary unit

21

P0

Inverter compressor maximum temp. protection

22

P1

High pressure protection

23

P2

Low pressure protection

Should ‘P2’ fault occur more than 3 times in 60 minutes, the 
unit will then display ‘H5’ fault

24

xP3

Compressor current protection

X represents a system, 1 is 

A system

, 2 is B system

25

P4

Discharge temp. protection

Should ‘P6’ fault occur more than 3 times in 100 minutes, 
the unit will then display ‘H6’ fault

26

P5

High condenser temp. protection

27

x (P6) 

Inverter module protection

X represents a system, 1 is 

A system

, 2 is B system. Should 

‘P6’ fault occur more than 3 times in 60 minutes, then the 
unit will display a ‘H4’ fault.  If ‘H4’ fault is displayed for more 
than 10 minutes, then ‘xP6’ fault will be displayed

28

P7

Main inverter current protection

29

P8

Auxiliary inverter current protection

30

P9

DC fan protection

Should ‘P9’ fault occur more than 3 times in 60 minutes, the 
unit will then display ‘H9’ fault

31

PL

Main inverter module temp. protection

32

xL0

DC compressor module error

X represents a system, 1 is 

A system

, 2 is 

B system

33

xL1

DC bus low pressure protection

X represents a system, 1 is 

A system

, 2 is 

B system

34

xL2

DC bus high pressure protection

X represents a system, 1 is 

A system

, 2 is 

B system

35

xL3

Reserve

X represents a system, 1 is 

A system

, 2 is 

B system

36

xL4

MCE error/synchronization/closed loop

X represents a system, 1 is 

A system

, 2 is 

B system

37

xL5

Zero speed protection

X represents a system, 1 is 

A system

, 2 is 

B system

38

xL6

Reserve

X represents a system, 1 is 

A system

, 2 is 

B system

39

xL7

Phase error protection

X represents a system, 1 is 

A system

, 2 is 

B system

40

xL8

Protection should the speed change be greater than 15 Hz before and 
after

X represents a system, 1 is 

A system

, 2 is 

B system

41

xL9

Protection should the required speed fluctuate by more than 15Hz

X represents a system, 1 is 

A system

, 2 is 

B system

Summary of Contents for CLIMATE 5000 VRF RDCI10/28-3

Page 1: ...itioning unit please read this manual carefully and keep it for future reference 6 720 862 438 2016 04 CLIMATE 5000 VRF RDCISeries AllDCInverterOutdoorUnits RDCI8 25 3 RDCI10 28 3 RDCI12 33 3 RDCI14 40 3 RDCI16 45 3 User Manual ...

Page 2: ...e tent person When a system is installed in a small room please install refrigerant leak detection equipment Should refrigerant come in to contact with a naked flame the gas can be extremely harmful Should a refrigerant leak occur switch off the power to the air conditioning unit Turn off any combustible heating devices ventilate the room and contact a competent person Do not use air conditioning ...

Page 3: ...eration the fan motor in the outdoor unit may stop running under high temperatures When a indoor unit is in standby the fan will stop running to avoid draft Defrost in the heating operation During heating operation frost can accumulate on the outdoor unit To increase efficiency the unit will start defrosting automatcally for approximately 2 10minutes depending on the amount of accumulated frost Th...

Page 4: ...discharge The master unit with slave units for different purposes when abnormal accident happen the director will illustrate When mode switches Indoor unit Bad odour Operation LED flashes No priority of Standby on panel is displayed Thawing frost light flashes in 30s Basic Checks Unit is operating at random periods Incorrect settings in the programmer No operation Checkthereisn torhasbeenaninterru...

Page 5: ... unit to clear the fault 19 C7 PL protection has been activated 3 times in 100 minutes Must restart electrical power supply to unit to clear the fault 20 xHd Auxiliary unit error X 1 2 3 e g 1Hd stands for auxiliary unit1 error X represents an auxiliary unit 21 P0 Inverter compressor maximum temp protection 22 P1 High pressure protection 23 P2 Low pressure protection Should P2 fault occur more tha...

Page 6: ...average temp Actual value 15 14 T3 pipe temp Left pipe temp Actual value 16 15 T5 pipe temp Right pipe temp Actual value 17 16 T4 ambient temp Actual value 18 17 Discharge temp of inverter compressor A Actual value 19 18 Discharge temp of inverter compressor B Actual value 20 19 Modual temp Actual value 21 20 Dischargepressurecorrespondingtothesaturationtemperature Actual value 30 22 21 The minimu...

Page 7: ...n speed 0 stop 1 15 speed increase sequentially 15 is the max fan speed EXV opening angle Pulse count Display value 8 State of the evaporator or condenser 0 close condenser 1 All evaporator 2 Left evaporator right condenser 3 Left evaporator close Night noise control mode 0 Night silent mode factory settings 1 silent mode 2 Super silent mode 3 No silent mode Static pressure mode 0 static pressure ...

Page 8: ......

Reviews: