Product Information
Climate 5000i – 6721824787 (2021/09)
54
2
Product Information
2.1
Declaration of conformity
The design and operating characteristics of this product comply with the
European and national requirements.
The CE marking declares that the product complies with all the
applicable EU legislation, which is stipulated by attaching this
marking.
The complete text of the Declaration of Conformity is available on the
Internet: worcester-bosch.co.uk.
2.2
Scope of delivery
Key to Fig. 1:
[1]
Outdoor unit (filled with refrigerant)
[2]
Indoor unit (filled with nitrogen)
[3]
Cold catalyst filter (black) and bio filter (green)
[4]
Drainage elbow with gasket (for outdoor unit with floor or wall
mounting bracket)
[5]
Remote control
[6]
Remote control holder with fixing screw
[7]
Fixing materials (5 screws and 5 wall plugs)
[8]
Set of printed documents for product documentation
[9]
5-core communication cable (optional accessory)
[10] 4 anti-vibration couplings for the outdoor unit
2.3
Product dimensions and minimum clearances
2.3.1
Indoor unit and outdoor unit
2.3.2
Refrigerant lines
Key to Fig. 5:
[1]
Gas-side pipe
[2]
Liquid-side pipe
[3]
Siphon-shaped elbow as oil separator
If the outdoor unit is positioned higher than the indoor unit, install a
siphon-shaped elbow on the gas side after no more than 6 m and every
6 m thereafter (
Fig. 5, [1]).
▶ Observe maximum pipe length and maximum difference in height
between indoor unit and outdoor unit.
Table 2 Pipe Length and Drop Height
Table 3 Pipe diameter depending on unit type
Table 4 Alternative pipe diameter
Table 5
2.4
Information on refrigerant
This device contains
fluorinated greenhouse gases
as refrigerant.
The device is hermetically sealed. You will find the information on the
refrigerant according to the Regulation (EU) No 517/2014 on
fluorinated greenhouse gases in the operating instructions of the device.
Information for the installer: If you refill refrigerant, enter the additional
charge size and the total charge size of the refrigerant in the table
“information on refrigerant” of the operating instructions.
Maximum pipe
length
1)
[m]
1) Gas side or liquid side
Maximum difference
in height
2)
[m]
2) Measured from lower edge to lower edge.
CL5000i 26 E
≤ 25
≤ 10
CL5000i 35 E
≤ 25
≤ 10
Pipe size
Unit type
Liquid side [mm]
Gas side [mm]
CL5000i 26 E
6.35 (1/4")
9.53 (3/8")
CL5000i 35 E
6.35 (1/4")
9.53 (3/8")
Pipe diameter [mm]
Alternative pipe diameter [mm]
6.35 (1/4")
6
9.53 (3/8")
10
Specification of the pipes
Min. piping length
3 m
Standard piping length
5 m
Additional refrigerant when the piping
length exceeds 5 m
12g/m
Piping Thickness
≥ 0.8 mm
Thickness of insulation against heat
≥ 6 mm
Material of insulation against heat
Polyethylene foam