Bosch Buderus SSB800SA | SSB1000SA | SSB1000TL Boilers Control Operations Guide
01.2020 | Bosch Thermotechnology Corp.
Data subject to change
5.1.2 Central Heating Mode 1
(On/Off with Outdoor Reset using dry contacts #9 and #10)
CH Mode “1”
- Boiler demand is generated thru a call for heat on low voltage
contacts #9 and #10 (dry contacts only). Boiler will target a system supply water
temperature equal to the corresponding point on the installer programmed heating
curve.
Central Heating
(CH) Mode
Description
Set these Parameters
Parameter #
Description
Default
Range
CH Mode = “1”
On/Off with reset water
temperature
1
CH Mode
0
0 - 5
109
Calc. Set point Offset
0°F
-1.8-1.8°F
5
Boiler Pump Overrun
30 sec.
0 – 900 sec.
7
CH Hysteresis Up
36°F
0-36°F
112
CH Hysteresis Down
9°F
0 - 36°F
9
Anti-cycle Period
180 sec.
10 – 900 sec.
10
Anti-cycle Temp Diff
28.8°F
0 - 36°F
14
Max Power CH
100%
50 - 100%
15
Min Power CH
1%
1 - 30%
19
Design Supply Temp
194°F
86 - 194°F
20
Design Outdoor Temp
23°F
-13 - 77°F
21
Baseline Supply Temp
104°F
68 - 194°F
22
Baseline Outdoor Temp
68°F
32- 86°F
23
Design Supply Min Limit
86°F
39.2 – 179.6°F
24
Design Supply Max Limit
194°F
80.6 - 194°F
25
Warm Weather Shut Dn
71.6°F
32- 95°F
26
Boost Temp Increment
0°F
0 - 54°F
27
Boost Temp Delay
20 min.
0 – 120 min.
Table 5
Figure 1
Design Supply Temp
(par. #19)
Design Supply
Min Limit
(par. #25)
Boiler S
upply Temper
atur
e ºF
Outdoor Air Temperature
Baseline Supply Temp
(par. #21)
Design Supply
Max Limit
(par. #24)
Design Outdoor Temp
(par. #20)
Baseline Outdoor Temp
(par. #22)
(par. #23)