1.
CONNECTING DIAGRAM
1.1.
BMS-BAC interfaces illustration
Ethernet interface, connect with BACnet/
IP network
1.2.
System connecting illustration
CAUTION
1) BMS-BAC net can connect to the centralised controller, or the
outdoor master unit. The address on the centralised controller
must be (0) and the outdoor master unit must be set to (16).
2) BMS-BAC net series must connect with Building Control
System with the same IP subnet! Otherwise the unit will not work
correctly.
2.
FUNCTION DESCRIPTION
This unit must be installed between the air conditioning system and
the BMS. BACnet interfaces create a way for air conditioning systems
to communicate with a BMS.
Once BACnet is configured correctly, any units connected to the
system will be able to be controlled and read with a BMS.
2.1.
Operation control
This unit will provide the BMS with seven setting functions including
‘operation mode selection’, ‘time on setting’, ‘time off setting’, ‘swing
function’. Refer to object table for more information.
CAUTION
There will be a 10-20 second delay for the BMS to send or read
information.
3.
CONFIGURATION ILLUSTRATION
Before using the BACnet, an initial setting configuration is required.
After installation is complete, you will need to input the IP address of
the BACnet into a web browser.
3.1.
Control setting
The local network code range will be between 0 and 63. The name
of the network will automatically configure, which can be changed
to something more memorable. After the demand has been set
and the equipment has been restarted, the equipment will modify the
changes. The control code has been set randomly before ex-factory,
“*” means of control code in “CONTROL-UNIT-*”.
3.2.
Time and date setting
You can set the time and date to all corresponding systems connected
to the BACnet. After setting the time and date, the system will require
restarting.
3.3.
Safe setting
If the controller requires resetting this can be achieved by using the
default admin password. Default administrator name is “admin” and
the password is “12345”.
CAUTION
For safety, passwords should be changed from the factory set
ones.
3.4.
Network setting
This device adapts Ethernet as the network interface. An IP address
of ‘192.168.1.8’ has been factory set which must be modified to the
appropriate network address.
CAUTION
BMS BAC net series must connect with a Building Control System
using the same IP subnet. Once IP has configured, click ‘apply’
and restart the equipment.
Four groups of 485 interfaces, each one connects with a
universal centralised monitor controller or Indoor/Outdoor
conditioning unit.
BMS-BAC
F1 F2 E
Indoor Central Controller
Outdoor Central Controller
BACnet/IP Network
CLIMATE 5000 VRF
6720862469 (16/04)
CONNECTING DIAGRAM
|
3