States text
BACnet ARRAY[N] CharacterString
PF
PE
PD
PC
PB
PA
P9
P8
P7
P6
P5
P4
P3
P2
P1
P0
No P
0
Time delay
Unsigned
1
O
Publicly type
Unsigned
1701
O
Event enable
BACnetEventTransitionBits
T T T
O
Affirm transform
BACnetEventTransitionBits
T T T
O
Notify Type
BACnetNotifyType
alarm
O
Operation instruction
The CURRENT VALUE attribute of the selected object reflects the current PROTECTION STATUS (it’s read only). In case of
the CURRENT VALUE shows as No P, that means the system without protection, while other information displaying means
the other relevant protection. For detail, please refer to TROUBLESHOOT & MAINTENANCE BROCHURE, or contact with
After-sales agent. Provided that more than one protection occurs simultaneously, only the minimal No. of the protection
would be showed. Thereinto, the CURRENT VALUE displays as 1 means P0; the CURRENT VALUE displays as 2 means P1,
analogously, the CURRENT VALUE displays as 3 means P2; the CURRENT VALUE displays as 16 means PF; the CURRENT
VALUE displays as 17 means No P.
CLIMATE 5000 VRF
6720862469 (16/04)
OBJECT TABEL
|
17