Advanced Settings
Heating & Cooling
u
To access the Heating and Cooling, click Advanced Settings, and enter the Professional Access Code
u
Click on a setting and use the scroll wheel to modify the default value. From this menu you can adjust:
TITLE
Default
Max
Min
Description
Fan Delay On
15 Seconds
120 Seconds
0 Seconds
The fan’s lag time after the heating or cooling call is initiated when in Fossil Fuel,
Heat Pump, or Cooling operation.
Fan Delay On Elec
0 Seconds
5 Seconds
0 Seconds
The fan’s lag time after the heating or cooling call is initiated when in Electric,
Auxiliary, or Emergency operation.
Fan Delay Off
60 Seconds
120 Seconds
30 Seconds
The fan’s lag time after the heating or cooling call is terminated.
Min. Run Time
5 Minutes
Stage Delay
3 Minutes
The minimum amount of time the system will cycle upon engagement.
Anti Short Cycle
5 Minutes
5 Minutes
0 Minutes
The Anti Short Cycle (ASC) timer represents the minimum amount of time the
system will remain off upon stage down engagement.
Cycle Time 180 Seconds 300 Seconds
60 Seconds
Time delay between active heating and cooling transition
Zero Energy
Band Heating
1° F/ 0.5° C
2° F/ 1° C
0.5° F/ 0.3° C A temperature range between the current temperature and the heating set point,
where heating is not engaged (also called deadband).
Zero Energy
Band Cooling
1° F/ 0.5° C
2° F/ 1° C
0.5° F/ 0.3° C A temperature range between the current temperature and the cooling set point,
where cooling is not engaged (also called deadband).