VENTING

Vent pipe connection.  WARNING: Do not reduce the vent pipe size.

The heater must be vented to the outside following all local ordinances and specifications for installing a gas appliance
vent or chimney. The heater must be located as close as practicable to a vertically rising chimney or vent that has a listed
vent cap at its termination point. The venting system must be designed and constructed so as to develop a positive flow
adequate to remove flue gasses to the outdoors.

Consult the National Fuel Gas Code if the vent will have elbows or share venting with another natural draft appliance.
The heater should never be common vented with a mechanically vented appliance. Single wall vent pipe is not
recommended, if used consult the National Fuel Gas Code.

Horizontally venting to a sidewall vent terminator or a vertically constructed vent stack along an outside wall of a building
is not permissible. A Powervent with a proof-of-draft safety interlock device, is required and is available in order to sidewall
vent.  Contact your dealer. 

In the Commonwealth of Massachusetts: Powervented applications must utilize proof-of-

draft safety interlock device.

VERTICAL GAS VENT:

 A 4 inch diameter gas vent constructed of double wall Type B gas vent is recommended.  Any gas vent

section that is greater than 45 degrees from the vertical is considered horizontal.  Horizontal sections must slope upwards
at least ¼ inch for every foot of its horizontal length and be properly supported.  Keep the horizontal section short and avoid
too many elbows.  The minimum vertical gas vent height allowed is 6 feet; horizontal vent connectors and elbows are not
to be considered in the total gas vent height.  All gas vent sections must be secured to each other with sheet metal screws
and be properly supported.

The gas vent constructed of double wall Type B gas vent must terminate above the roof surface with a listed vent cap at
a height that’s in accordance with Figure A or B and their table, provided they are at least 8 feet (2.4 m) from a vertical wall
or similar obstruction.  All other gas vents that are not able to terminate within the minimum specified height allowed must
terminate not less than 2 feet (0.6 m) above the highest point where it’s passed through the roof and at least 2 feet (0.6
m) higher than any vertical wall or similar obstruction within 10 feet (3.1 m).

Roof pitch

H (minimum) feet

meters

Flat to 6/12

1.0

0.30

6/12 to 7/12

1.25

0.38

Over 7/12 to 8/12

1.5

0.46

Over 8/12 to 9/12

2.0

0.61

Over 9/12 to 10/12

2.5

0.76

Over 10/12 to 11/12

3.25

0.99

Over 11/12 to 12/12

4.0

1.22

Over 12/12 to 14/12

5.0

1.52

Over 14/12 to 16/12

6.0

1.83

Over 16/12 to 18/12

7.0

2.13

Over 18/12 to 20/12

7.5

2.27

Over 20/12 to 21/12

8.0

2.44

GAS VENT TERMINATIONS FOR LISTED VENT CAPS

LISTED VENT CAP

LISTED VENT CAP

LISTED GAS VENT

LOWEST DISCHARGE OPENING

H (minimum) height
from roof to lowest
discharge opening

Figure A

Figure B

ROOF PITCH

IS X/12

12

X

Summary of Contents for AquaStar 38B LP

Page 1: ...sing property damage personal injury or death FOR YOUR SAFETY Do not store or use gasoline or other flammable combustible or corrosive vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follo...

Page 2: ...ition BOSCH is constantly improving our products therefore specifications are subject to change without prior notice AquaStar 38B LP and 38B NG Specifications Gas Input max 40 000 Btu hr min 20 000 Btu hr Water Connection 1 2 Thread fitting NPT H x W x D 25 3 8 x 10 5 8 x 9 1 8 Vent 4 Gas Connection 1 2 NPT thread Min Water Pressure 13 Psi at 1 3 GPM Max Water Pressure 150 Psi Shipping Weight 20 L...

Page 3: ...6 720 606 446 MINIMUM INSTALLATION CLEARANCES FROM COMBUSTIBLE AND NON COMBUSTIBLE MATERIALS FRONT VIEW SIDE VIEW AQUASTAR MODEL 38B MODEL 38B TOP A 12 FRONT B 4 BACK 0 SIDES 4 FLOOR C 12 VENT DIAMETER 4 ...

Page 4: ...or your safety and for proper heater operation you must provide an abundant supply of combustion air and a proper venting installation The heater may still operate even when improperly vented It will however be less efficient and could eventually damage the heater It could even result in human sickness or death due to oxygen deprivation and carbon monoxide poisoning Follow the guidelines below 1 P...

Page 5: ...tight construction all air should be taken from outside That would be 2000 cubic feet for the Aquastar 38B alone CLEARANCES The Aquastar 38 B is design certified for installation on a combustible wall and for installation in an alcove or closet with the minimum clearances to combustible and non combustible construction listed below A Top 12 inches 305 mm B Front 4 inches 102mm C Back 0 inches D Si...

Page 6: ...In unconfined spaces in buildings of conventional frame masonry or metal construction infiltration is normally adequate to provide air for combustion ventilation and dilution of flue gasses Identification labels are found on the shipping box and on the rating plate which is located on the right side panel of the cover Also each burner orifice is stamped with a number 79 for LPG and 120 for Natural...

Page 7: ... Horizontal sections must slope upwards at least inch for every foot of its horizontal length and be properly supported Keep the horizontal section short and avoid too many elbows The minimum vertical gas vent height allowed is 6 feet horizontal vent connectors and elbows are not to be considered in the total gas vent height All gas vent sections must be secured to each other with sheet metal scre...

Page 8: ...ollar must be used when penetrating a masonry chimney A Existing INTERIOR Masonry Chimney The metal gas vent pipe should be permanently mounted inside the masonry chimney Double wall Type B gas vent is recommended The masonry chimney may have to be tile or metal lined before the insertion of the gas vent pipe check local codes for clarification The lining material must be listed for use only with ...

Page 9: ...as to which it will be connected In the United States The installation must conform with local codes or in the absence of local codes the National Fuel Gas Code ANSI Z223 1 NFPA 54 In Canada The Installation should conform with CGA B149 INSTALLATION CODES and or local installation codes NOTE The Aquastar 38 B is supplied with a gas pressure regulator that must be installed on the heater before att...

Page 10: ...eak NOTE Do not apply soap solution to pilot filter screen or pilot orifice area If you have a leak shut off the gas After verifying that required gaskets are in place tighten appropriate fittings to stop leak Turn the gas on and check again with a soapy solution Never test for gas leaks using a match or flame MAXIMUM INLET GAS FLOW PRESSURE SETTING Above 4 500 ft consult your local gas supplier F...

Page 11: ...idual shut off valve OPERATINGINSTRUCTIONS Before proceeding with the operation of the heater make sure that the system is filled with water Open the cold water inlet supply to the heater fully Open a hot water faucet to permit the water to fill the heater and the piping and to eliminate the air trapped in the system Close the hot water faucet after the water flows freely and all the air has escap...

Page 12: ...emperature adjustment knob and unscrew and remove the knob collar Unscrew the central screw located at the bottom of the front cover Pull main cover out toward you and lift up and out Pull the air screen off wash it and blow any lint off See Fig 8 The pilot orifices should also be cleaned or replaced Do not enlarge the orifice Do not use any wire or sharp object to clean orifices Natural gas orifi...

Page 13: ...ved During this process press on the piezo ignition button separately until the pilot flame has ignited Main Burner Flames The main burner flames should be blue with a more intense blue cone in the center core Yellow flames could be a sign of wrong size gas orifices or dirty burners or a blockage on the heat exchangers fins If some burners have yellow flames while others have good flames it is lik...

Page 14: ...person to clean water valve or replace if corrosion is present PILOT LIGHTS BUT FLAME GOES OUT WHEN BUTTON IS RELEASED 1 Pilot push button was not pushed in far enough or was not held in long enough Slide the gas valve button to pilot position and depress this button Hold it pushed in for at least 15 seconds to give time for the pilot flame to properly heat the tip of the thermocouple 2 Pilot flam...

Page 15: ...s pressure too low Very low gas pressure may be caused by low delivered gas pressure a jammed gas regulator or undersized gas lines If the gas lines are undersized there may still be the specified static gas line pressure However when the water valve opens and gas enters the burners the pressure could drop sharply causing the pilot flame to go out Have a gas technician confirm the gas pressure bot...

Page 16: ...0 1 7 9 11 1 Heat exchanger 2 Pilot assembly 3 Burner manifold gas pressure test nipple 4 Pilot gas tubing 5 Main gas burner 6 Inlet gas pressure test nipple 7 Gas valve 8 Gas control slide 9 Piezo igniter 10 Temperature adjustment knob 11 Water valve 3 5 6 ...

Page 17: ...17 6 720 606 446 ...

Page 18: ...18 6 720 606 446 Fig 10 INTERIOR COMPONENTS DIAGRAM AND PARTS LIST ...

Page 19: ...051 11a Pilot air screen 8 700 507 055 12 Pilot orifice 8 708 200 005 NG 8 748 200 173 LPG 13 Pilot Tube 8 710 707 166 14 Thermocouple 8 747 202 083 15 Gas valve 8 707 011 456 LPG Gas valve 8 707 011 466 NG 16 Electromagnet 8 707 201 012 17 Thermocable 8 747 202 209 18 Water valve assembly 8 707 002 497 19 Pushrod 8 703 406 204 20 Water valve diaphragm 8 700 503 050 21 Slow ignition valve 8 708 50...

Page 20: ...20 6 720 606 446 Fig 11 Flow chart of Aquastar 38 B ...

Page 21: ...urnish a replacement part free of charge Shipping costs In addition to supplying the replacement part s BBTNA will provide ground service delivery for these parts Expedited or upgraded shipping will be charged to the customer Service labor costs This warranty does not cover any labor costs associated with service removal or re installation of part s All such costs must be borne by the Purchaser Ad...

Page 22: ...22 6 720 606 446 ...

Page 23: ...23 6 720 606 446 ...

Page 24: ... E T A W D L I U B E R N E E R C S R E T L I F R E T A W T C E P S N I Y L B M E S S A T O L I P T C E P S N I Y L B M E S S A T N E V T C E P S N I R E N R U B N I A M T C E P S N I Replacement Parts available from BBT NORTH AMERICA Bosch Group Bosch Water Heating 340 Mad River Park Waitsfield VT 05673 Phone 800 642 3111 Fax 802 496 6924 www boschhotwater com techsupport boschhotwater com 2006 BB...

Reviews: