background image

4

6 720 606 446

GENERAL RULES TO FOLLOW
FOR SAFE OPERATION

1.

You should follow these instructions when you install your

heater.  In the United States: The installation must conform
with local codes or, in the absence of local codes, the
National Fuel Gas Code ANSI Z223.1/NFPA 54.
In Canada: The Installation should conform with CGA
B149.(1,2) INSTALLATION CODES and /or local installation
codes.

2.

Carefully plan where you install the heater. Correct

combustion air supply and flue pipe installation are very
important. If not installed correctly, fatal accidents can be
caused by lack of air, carbon monoxide poisoning or fire.

3.

The place where you install the heater must have enough

ventilation. The National Fire Codes do not allow gas fired
water heater installation in bathrooms, bedrooms or any
occupied rooms normally kept closed. See the section below
on locating the heater. The 38B is not approved for boat or
RV installations.

4.

You must vent your heater. See section on VENTING,

Page 6.

5.

The appliance  must be disconnected from the gas supply

piping system during any pressure testing  at pressures in
excess of 1/2 Psig (3.5 kPa).
The appliance must be isolated from the gas supply piping
system by closing its individual manual shutoff valve during
any pressure testing of the gas supply piping system at test
pressures equal to or more than 1/2 Psig (3.5Kpa).  The
appliance and its gas connection must be leak tested before
placing the appliance in operation.

6.

Keep water heater area clear and free from combustibles

and flammable liquids. Do not locate the heater over any
material which might burn.

7. Correct gas pressure

 is critical for the optimum

operation of this heater (see specifications on page 2). Gas
piping must be sized to provide the required pressure at the
maximum output of the heater, while all the other gas
appliances are in operation. Check with your local gas
supplier, and see the section on connecting the gas supply.

8.

Should overheating occur or the gas supply fail to shut

off, turn off the gas supply at the manual gas shut off valve
on the gas line.

9.

Do not use this appliance if any part has been underwater.

Immediately call a qualified service technician to inspect
the appliance and to replace any part of the control system
and any gas control which has been underwater.

PROPER LOCATION FOR INSTALLING YOUR
HEATER

Carefully select the location of your new heater. For your
safety and for proper heater operation, you must provide an
abundant supply of combustion air and a proper venting
installation.
The heater may still operate even when improperly vented.
It will, however, be less efficient and could eventually damage
the heater. It could even result in human sickness or death
due to oxygen deprivation and carbon monoxide poisoning.

 Follow the guidelines below:

1.

Place your heater as close to a vent or chimney as

possible.

2.

National building codes require that you do not install

this appliance in bathrooms, bedrooms, unvented closet or
any occupied rooms normally kept closed. The 38B is not
approved for boat or RV installations.

3.

Simultaneous operation of other appliances such as

exhaust fans, ventilation systems clothes dryers, fireplaces
or wood stoves  could create a vacuum effect in your home
which could cause dangerous combustion by-products to
spill back into your home rather than venting to the outside
through the flue. Confirm that your Aquastar is venting
properly when all these other appliances are running. See
section on venting.

Do not obstruct the flow of combustion and ventilation
air to the appliance.

  If installed near a clothes dryer it is

very important that the dryer be properly vented. Failure to
properly vent a dryer could result in a gradual accumulation
of lint on the water heater fin coils and burners, leading to a
dangerous condition of vent blockage and poor unsafe
combustion.

4.

Your hot water lines should be kept short to save energy.

It is always best to have hot water lines insulated.

WARNING:

 

The water in this water heater is cold

and always remains cold exept  for the times that hot water
is being used

 

DO NOT INSTALL IN  AN AREA WHERE IT

COULD FREEZE.
This heater is neither designed for nor approved for
outside installation

.

Drain the heater entirely if freezing temperatures are
anticipated in area where heater is installed by disconnecting
both the inlet and outlet water connections. Additionally,
remove the drain plug under the water valve. See Fig 0.

WARNING: Flammable materials, gasoline,

pressurized containers, or any other items or articles
that are potentially fire hazards must NOT be placed on
or adjacent to the heater.  The appliance area must be
kept free of all combustible materials, gasoline and other
flammable vapors and liquids.
This product is not approved for manufactured homes
(mobile home), recreational vehicles (RV) or boats.
Reference ANSI Z21.10.3.
This product is neither designed or approved for outside
installations.

Fig. 0 - Water heater drain plug

WATER VALVE

DRAIN PLUG

TO HEAT

EXCHANGER

Summary of Contents for AquaStar 38B LP

Page 1: ...sing property damage personal injury or death FOR YOUR SAFETY Do not store or use gasoline or other flammable combustible or corrosive vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follo...

Page 2: ...ition BOSCH is constantly improving our products therefore specifications are subject to change without prior notice AquaStar 38B LP and 38B NG Specifications Gas Input max 40 000 Btu hr min 20 000 Btu hr Water Connection 1 2 Thread fitting NPT H x W x D 25 3 8 x 10 5 8 x 9 1 8 Vent 4 Gas Connection 1 2 NPT thread Min Water Pressure 13 Psi at 1 3 GPM Max Water Pressure 150 Psi Shipping Weight 20 L...

Page 3: ...6 720 606 446 MINIMUM INSTALLATION CLEARANCES FROM COMBUSTIBLE AND NON COMBUSTIBLE MATERIALS FRONT VIEW SIDE VIEW AQUASTAR MODEL 38B MODEL 38B TOP A 12 FRONT B 4 BACK 0 SIDES 4 FLOOR C 12 VENT DIAMETER 4 ...

Page 4: ...or your safety and for proper heater operation you must provide an abundant supply of combustion air and a proper venting installation The heater may still operate even when improperly vented It will however be less efficient and could eventually damage the heater It could even result in human sickness or death due to oxygen deprivation and carbon monoxide poisoning Follow the guidelines below 1 P...

Page 5: ...tight construction all air should be taken from outside That would be 2000 cubic feet for the Aquastar 38B alone CLEARANCES The Aquastar 38 B is design certified for installation on a combustible wall and for installation in an alcove or closet with the minimum clearances to combustible and non combustible construction listed below A Top 12 inches 305 mm B Front 4 inches 102mm C Back 0 inches D Si...

Page 6: ...In unconfined spaces in buildings of conventional frame masonry or metal construction infiltration is normally adequate to provide air for combustion ventilation and dilution of flue gasses Identification labels are found on the shipping box and on the rating plate which is located on the right side panel of the cover Also each burner orifice is stamped with a number 79 for LPG and 120 for Natural...

Page 7: ... Horizontal sections must slope upwards at least inch for every foot of its horizontal length and be properly supported Keep the horizontal section short and avoid too many elbows The minimum vertical gas vent height allowed is 6 feet horizontal vent connectors and elbows are not to be considered in the total gas vent height All gas vent sections must be secured to each other with sheet metal scre...

Page 8: ...ollar must be used when penetrating a masonry chimney A Existing INTERIOR Masonry Chimney The metal gas vent pipe should be permanently mounted inside the masonry chimney Double wall Type B gas vent is recommended The masonry chimney may have to be tile or metal lined before the insertion of the gas vent pipe check local codes for clarification The lining material must be listed for use only with ...

Page 9: ...as to which it will be connected In the United States The installation must conform with local codes or in the absence of local codes the National Fuel Gas Code ANSI Z223 1 NFPA 54 In Canada The Installation should conform with CGA B149 INSTALLATION CODES and or local installation codes NOTE The Aquastar 38 B is supplied with a gas pressure regulator that must be installed on the heater before att...

Page 10: ...eak NOTE Do not apply soap solution to pilot filter screen or pilot orifice area If you have a leak shut off the gas After verifying that required gaskets are in place tighten appropriate fittings to stop leak Turn the gas on and check again with a soapy solution Never test for gas leaks using a match or flame MAXIMUM INLET GAS FLOW PRESSURE SETTING Above 4 500 ft consult your local gas supplier F...

Page 11: ...idual shut off valve OPERATINGINSTRUCTIONS Before proceeding with the operation of the heater make sure that the system is filled with water Open the cold water inlet supply to the heater fully Open a hot water faucet to permit the water to fill the heater and the piping and to eliminate the air trapped in the system Close the hot water faucet after the water flows freely and all the air has escap...

Page 12: ...emperature adjustment knob and unscrew and remove the knob collar Unscrew the central screw located at the bottom of the front cover Pull main cover out toward you and lift up and out Pull the air screen off wash it and blow any lint off See Fig 8 The pilot orifices should also be cleaned or replaced Do not enlarge the orifice Do not use any wire or sharp object to clean orifices Natural gas orifi...

Page 13: ...ved During this process press on the piezo ignition button separately until the pilot flame has ignited Main Burner Flames The main burner flames should be blue with a more intense blue cone in the center core Yellow flames could be a sign of wrong size gas orifices or dirty burners or a blockage on the heat exchangers fins If some burners have yellow flames while others have good flames it is lik...

Page 14: ...person to clean water valve or replace if corrosion is present PILOT LIGHTS BUT FLAME GOES OUT WHEN BUTTON IS RELEASED 1 Pilot push button was not pushed in far enough or was not held in long enough Slide the gas valve button to pilot position and depress this button Hold it pushed in for at least 15 seconds to give time for the pilot flame to properly heat the tip of the thermocouple 2 Pilot flam...

Page 15: ...s pressure too low Very low gas pressure may be caused by low delivered gas pressure a jammed gas regulator or undersized gas lines If the gas lines are undersized there may still be the specified static gas line pressure However when the water valve opens and gas enters the burners the pressure could drop sharply causing the pilot flame to go out Have a gas technician confirm the gas pressure bot...

Page 16: ...0 1 7 9 11 1 Heat exchanger 2 Pilot assembly 3 Burner manifold gas pressure test nipple 4 Pilot gas tubing 5 Main gas burner 6 Inlet gas pressure test nipple 7 Gas valve 8 Gas control slide 9 Piezo igniter 10 Temperature adjustment knob 11 Water valve 3 5 6 ...

Page 17: ...17 6 720 606 446 ...

Page 18: ...18 6 720 606 446 Fig 10 INTERIOR COMPONENTS DIAGRAM AND PARTS LIST ...

Page 19: ...051 11a Pilot air screen 8 700 507 055 12 Pilot orifice 8 708 200 005 NG 8 748 200 173 LPG 13 Pilot Tube 8 710 707 166 14 Thermocouple 8 747 202 083 15 Gas valve 8 707 011 456 LPG Gas valve 8 707 011 466 NG 16 Electromagnet 8 707 201 012 17 Thermocable 8 747 202 209 18 Water valve assembly 8 707 002 497 19 Pushrod 8 703 406 204 20 Water valve diaphragm 8 700 503 050 21 Slow ignition valve 8 708 50...

Page 20: ...20 6 720 606 446 Fig 11 Flow chart of Aquastar 38 B ...

Page 21: ...urnish a replacement part free of charge Shipping costs In addition to supplying the replacement part s BBTNA will provide ground service delivery for these parts Expedited or upgraded shipping will be charged to the customer Service labor costs This warranty does not cover any labor costs associated with service removal or re installation of part s All such costs must be borne by the Purchaser Ad...

Page 22: ...22 6 720 606 446 ...

Page 23: ...23 6 720 606 446 ...

Page 24: ... E T A W D L I U B E R N E E R C S R E T L I F R E T A W T C E P S N I Y L B M E S S A T O L I P T C E P S N I Y L B M E S S A T N E V T C E P S N I R E N R U B N I A M T C E P S N I Replacement Parts available from BBT NORTH AMERICA Bosch Group Bosch Water Heating 340 Mad River Park Waitsfield VT 05673 Phone 800 642 3111 Fax 802 496 6924 www boschhotwater com techsupport boschhotwater com 2006 BB...

Reviews: