RS-485 host interface
The RS-485 host interface of the controller can be set for using a 2- or 4-wire connection. Up
to eight controllers can be used on one host bus.
1
5
3
2
4
RS 485
RS 232
Figure 4.9:
Configuration of a RS-485 host system
Position
Description
1
Host
2
RS-485 bus
3
Access Modular Controller
The following conditions apply for a RS-485 bus system:
–
A bus system consists of a bus line and/or one or more branch lines.
–
Cable lengths exceeding 100 m (300 ft) must be installed as bus lines.
–
Branch lines are branching connections from a bus line.
–
Peripheral devices are controllers which are connected to the host computer.
–
Maximum cable length of a bus line must not exceed 1200 m (4000 ft).
–
The cable length of branch lines must not exceed 100 m (330 ft).
To use RS-485 mode at the controller, connect the data cables to the pluggable screw
connector of the RS-485 host interface.
Figure 4.10:
RS-485 host interface