Mounting method
Stora – 6721835341 (2021/04)
34
5.2.3
Connection on the water side
NOTICE
Damage to cylinder connections due to contact corrosion.
▶ If copper is used for the connection on the domestic water side: use
a connection fitting made of brass or gunmetal.
▶ Make the cold water connection in accordance with DIN 1988-100
using suitable individual fittings or a complete safety assembly.
▶ The type-tested pressure-relief valve must be able to blow off at least
the volumetric flow rate that is limited by the volumetric flow rate set
at the cold water inlet (
▶ Set the type-tested pressure-relief valve so that the permissible
cylinder operating pressure cannot be exceeded.
▶ Terminate the discharge pipe where it will be easily visible in the
frost-proof area via a dewatering point. The discharge pipe must be at
least equal to the outlet cross-section of the pressure relief valve.
NOTICE
Damage due to positive pressure!
▶ If using a non-return valve: install a pressure-relief valve between the
non-return valve and the cylinder connection (cold water).
▶ Never close the blow-off opening of the pressure-relief valve.
▶ Fit a sign near the discharge pipe of the pressure-relief valve with the
following warning: "For safety reasons, water may be expelled from
the discharge pipe during heating! Do not close!"
If the static system pressure exceeds 80 % of the pressure relief valve
excess pressure:
▶ Install a pressure reducer upstream.
5.2.4
DHW expansion vessel
To avoid water loss via the pressure-relief valve, a suitable expansion
vessel can be installed for potable water.
▶ Install the expansion vessel in the cold water line between the
cylinder and the safety assembly. Potable water must flow through
the expansion vessel each time DHW is drawn off.
The following table serves as a guide for sizing an expansion vessel. Sizes
may deviate for other makes of expansion vessel with different useful
capacities. Details refer to a cylinder temperature of 60 °C.
Table 18 Guide, expansion vessel
5.3
Electrical connection
DANGER
Risk to life due to electric shock!
▶ Prior to establishing the electrical connection, isolate the heating
system from the power supply (230 V AC).
For a detailed description of the electrical connection, see the relevant
installation instructions.
Connection to a wall mounted boiler
▶ Connect the plug of the cylinder temperature sensor to the wall
mounted boiler (
Figure 7, page 60).
5.4
Connection diagram
Fig. 2
Connection diagram on the domestic water side
BWAG DHW expansion vessel (recommendation)
E
Drain work
KW
Cold water connection
R
SP
Cylinder return
V
SP
Cylinder flow
SG
Safety assembly to DIN 1988-100
WW
DHW outlet
ZL
DHW circulation connection
10
Water pressure relief valve
14
Discharge pipe
15.1 Test valve
15.2 Non-return component
15.3 Pressure gauge connector
20
On-site DHW circulation pump
21
Shut-off valve (on-site)
22
Pressure reducer (if required, accessory)
Cylinder type
Vessel
pre-charge
pressure =
cold water
pressure
Vessel size in litres
according to the excess
pressure of the pressure-
relief valve
6 bar
8 bar
10 bar
WP 400 PK
4 bar
33
18
18
WP 500 P
4 bar
60
25
18
WP 700 P
4 bar
60
33
25
Summary of Contents for 8735100975
Page 57: ...57 Stora 6721835341 2021 04 2 0010037827 001 1 1 13 2 3 4 9 10 11 13 14 12 8 5 6 7 ...
Page 59: ...59 Stora 6721835341 2021 04 4 1 WP 400 PK 2 WP 500 P 0010037816 001 5 6 ...
Page 60: ...Stora 6721835341 2021 04 60 7 8 ...
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ...Bosch Thermotechnik GmbH Junkersstrasse 20 24 D 73249 Wernau www bosch thermotechnology com ...