6 720 644 930
Installation instructions
9
3
Installation instructions
3.1
Specialized tools
The following specialized tools may be required for
installation:
• Manometer
• Multi-meter
• Combustion Gas Analyzer.
3.2
Introduction
Please follow these instructions. Failure to follow
instructions may result in:
B
Damage or injury.
B
Improper operation.
B
Loss of warranty.
If you are unable to perform the tasks required to install
this heater properly, please contact a locally licensed
plumber or gas technician.
3.3
Venting
3.3.1
Vent material
Establish vent clearances that comply with the vent
manufacturer's specifications. In all cases, follow local
codes. See Table 2.
Horizontal venting systems only:
An optional stainless concentric vent/air intake
termination can be used to provide only one penetration
point through the exterior wall (see Fig. 8, 9 & 10). The
concentric vent/air intake kit can be ordered from your
local wholesaler. (Part# ESHCK). Note: Only tee
terminals are approved for use with the
concentric vent/air intake kit (see Table 3). Vent
piping and tee terminal used with kit must be
from the same vent pipe manufacturer. The
appliance can also be installed with separate air
intake and exhaust piping (see Fig. 16
).
i
Common installation practice is to deter-
mine the venting/intake system layout and
penetration and then work back to the
heater.
Warning: Do not reduce the vent
(exhaust and combustion) pipe sizes
and do not common vent with any other
vented appliance or stove.
Warning: Failure to vent the exhaust
gases to the outside with sealed
stainless steel vent pipe (AL29-4C)
may result in dangerous flue gases
filling the structure in which it is
installed.
Warning: Do not mix vent pipe or
joining methods from different
manufacturers.
Warning: Approved terminators must
be used for inlet and exhaust vent sys-
tems to prevent rain from entering the
appliance. Failure to do so may result in
damage to the appliance. This failure is
not covered under the manufacturer’s
warranty.
Caution: The vent system must be
installed by a qualified installer in
accordance with these instructions. If
improperly installed, a hazardous
condition such as explosion or carbon
monoxide poisoning could result.
Bosch Water Heating will not be
responsible for improperly installed
appliances.
Warning: In areas where outside
temperatures routinely come close to
freezing, sealed combustion operation
is required. Use separate terminations
for combustion and vent, which must be
installed on the same wall or roof
surface, however never facing the
direction of prevailing winds. Failure to
do so may result in heat exchanger
freezing up and bursting. This failure is
not covered under the manufacturer's
warranty.
Diam.
Material
Exhaust
Vent
3 or 4 inches
Sealed single wall stainless steel
(AL29-4C)
Intake
Vent
3 or 4 inches Sealed PVC or any other rigid pipe
Table 2 Venting Specifications