6 720 644 930
10
Installation instructions
Fig. 8
Concentric kit part # ESHCK
Fig. 9
Concentric kit vent assembly
Fig. 10 Concentric kit installation
3.3.2
Venting Specifications
Install appliance as close to point of vent termination as
possible. The exhaust piping must vent directly to the
outside of the structure.
Horizontal sections of vent must pitch upward towards
termination ¼" for every foot of horizontal length, to
prevent the pooling of condensate, and be supported at
4 foot intervals with overhead hangers.
Exception: horizontal run between last elbow and
termination must pitch down to termination 1/4" per
foot. Note: For horizontal terminations, venting must
terminate once it penetrates to the outside of the
structure. There must be no sections of vent pipe
exposed to the outdoors other than the termination.
Note: Listed thimbles or collars are necessary where
venting passes through wall and ceiling partitions. If the
vent system passes through combustible areas where
the vent clearance requirements cannot be maintained,
it is permissible to chase straight sections of sealed 3
inch single wall vent through 4 inch (or greater) Type-B
vent. The distance to combustibles using this chase
technique is 1 inch. Note: Type-B vent must never be
used as the actual exhaust vent system for the
appliance, as it is not gas tight and illegal for use with
this appliance. This will create a serious health hazard
and void the warranty.
For specific questions concerning vent material, speci-
fications, usage or installation, please contact the vent
manufacturer directly.
6720608782-09.1Av
6720608782-10.1Av
12"
6720608782-11.1Av
3” stainless steel pipe
3”
VENTING
Z flex
Protech
Heat Fab
3"
90° elbow
2SVEEWCF0390
FSELB9003
9314
3" Tee
Terminal
2SVSTTF03
FSTT3
9390TEE
3”
Horizontal
Terminal
2SVSTB03
FSTB3
N/A
3" horiz.
terminal
with damper
2SVSHTD03
N/A
N/A
3” Vertical
Terminal
2SVSRCF03
FSRC3
5300CI
Table 3 3" Terminator Part Numbers
4”
VENTING
Z flex
Protech
Heat Fab
4"
90° elbow
2SVEEWCF0490
FSELB9004
9414
4" Tee
Terminal
2SVSTTF04
FSTT4
9490TEE
4”
Horizontal
Terminal
2SVSTB04
FSTB4
N/A
4" horiz.
terminal
with damper
2SVSHTD04
FSRC4
5400CI
4"
vertical
terminal
2SVSRCF04
N/A
N/A
Table 4 4" Terminator Part Numbers