6.1 Online mode
The LCD display in Online mode is shown in the following diagram.
The information about the mains power, the battery, the UPS output
and the load is displayed. The “Line” and “2” code indicate the UPS is
working in Online mode.
If the output is overloaded, the load percent is shown and the audible
alarm will bleep twice every second. You should switch off
unnecessary load one by one to decrease the load connected to the
UPS ideally less than 90% of its nominal power capacity.
Note: Please see following if running the UPS from a diesel
generator
:
●
Activate the generator and wait for the engine to stabilize before
supplying power to the UPS. Turn on the UPS according to the
start-up procedure. After the UPS is turned on, then the loads can
be connected to the UPS one by one.
●
The power capacity of the AC generator should be at least twice of
the UPS capacity.
■
■
■
■