-12-
5. Connection and Operation
5.1 Inspection:
Inspect the packaging carton and its contents for damage. Please
inform the transport agency immediately should you find signs of
damage.
Please keep the packaging in a safe place for future use.
5.2 Connection:
(1) UPS Input Connection
If the UPS is connected via the supplied input power cable, please
connect to a socket which has necessary protection and capacity:
over 6A for B400-010-B and B400-010-C, over 7A for B400-020-B,
13A for B400-020-C, B400-030-B, and B400-030-C.
If the UPS is being hardwired, the correct cable and protective
safety device should be selected.
When selecting the protective device, the user can refer to below
table for detailed information when installation.
UPS INPUT ISOLATOR
Model No.
VOLTAGE
CURRENT
B400-010-C
240 VAC
10A
B400-020-C
240 VAC
20A
B400-030-C
240 VAC
32A
If electrical wiring is required the system must be installed to
local safety standards by qualified electricians.